Diagnostics
80
RTAF-SVX001A-EN
Comm Loss: Condenser
Refrigerant Pressure
Comm Loss: Condenser
Rfgt Pressure
Comm: Cond Rfgt
Pressure
Circuit
Immediate Latch
All
Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period.
Remote
Comm Loss: Condenser
Refrigerant Tank Valve
Comm Loss: Cond Rfgt
Tank Valve
Comm: Cond Rfgt Tank
Vlv
Circuit
Normal
Latch
All
Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period.
Remote
Comm Loss: Electronic
Expansion Valve
Comm: EXV
Circuit
Normal
Latch
All
Continual loss of communication between the MP and the EXV
Step Status has occurred for a 30 second period, OR EXV
Steps Maximum Position has not been received. If EXV Steps
Maximum Position has not been received, MP will periodically
request EXV Steps Maximum Position, since it is only
transmitted upon request.
Remote
Comm Loss: Emergency
Stop Feedback Input
Comm: Emergency Stop
Chiller
Normal
Latch
All
Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period.
Remote
Comm Loss: Energy Meter
Pulse Input
Comm: Energy Pulse
Input
None
Info
Latch
All
Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period.
Remote
Comm Loss: Evaporator
Entering Water Pressure
Comm Loss: Evap
Entering Water Pressure
Comm: Evap Ent Water
Press
Chiller
Info
Latch
All
Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period.
Remote
Comm Loss: Evaporator
Entering Water
Temperature
Comm Loss: Evap
Entering Water Temp
Comm: Evap Ent Water
Temp
Chiller
Normal
Latch
All
Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period. Note:
Entering Water Temp Sensor is used in EXV pressure control
as well as ice making & CHW reset, so it must cause a unit
shutdown even if Ice or CHW reset is not installed.
Remote
Comm Loss: Evaporator
Isolation Valve Close
Switch
Comm Loss: Evap Iso
Valve Close Switch
Comm: Evap Iso Vlv Close
Sw
Circuit
Immediate Latch
All
Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period.
Remote
Comm Loss: Evaporator
Isolation Valve Open
Switch
Comm Loss: Evap Iso
Valve Open Switch
Comm: Evap Iso Vlv Open
Sw
Circuit
Immediate Latch
All
Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period.
Remote
Comm Loss: Evaporator
Isolation Valve Relay
Comm Loss: Evap
Isolation Valve Relay
Comm: Evap Iso Valve
Relay
Circuit
Immediate Latch
All
Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period.
Remote
Comm Loss: Evaporator
Leaving Water Pressure
Comm Loss: Evap Leaving
Water Pressure
Comm: Evap Leav Water
Press
Chiller
Info
Latch
All
Continual loss of communication between the MP and the
Functional ID has occurred for a 30 second period.
Remote
Table 28.
Communications diagnostics (continued)
Diagnostic Name
Affects
Target Severity Persistence
Active
Modes
[Inactive
Modes]
Criteria
Reset
Level