Diagnostics
70
RTAF-SVX001A-EN
Main Processor Diagnostics
Table 27.
Main processor diagnostics
Diagnostic
Name
Affects
Target Severity Persistence
Active
Modes
[Inactive
Modes]
Criteria
Reset
Level
AFD%RLA
Feedback - xA
Cprsr
Normal
Latch
All
Out-Of-Range Low or Hi or bad LLID
Remote
BAS
Communication
Lost
Chiller
Info and
Special
Action
NonLatch
All
The BAS was setup as “installed” at the MP and the Lontalk LCIC lost
communications with the BAS for 15 contiguous minutes after it had
been established. Refer to Section on Setpoint Arbitration to determine
how setpoints and operating modes may be affected by the comm loss.
The chiller follows the value of the Tracer Default Run Command which
can be previously written by Tracer and stored nonvolatilely by the MP
(either use local or shutdown). Note that this diagnostic is never
operational for BacNet Communication interface (BCIC) and only
operational with a LonTalk Communication interface (LCIC) if so
configured by the BAS or Tracer system.
Remote
BAS Failed to
Establish
Communication
BAS Failed to
Establish Comm
Chiller
Info and
Special
Action
NonLatch
At power-up
The BAS was setup as “installed” and the BAS did not communicate with
the Lontalk LCIC within 15 minutes after chiller controls power-up.
Refer to Section on Setpoint Arbitration to determine how setpoints and
operating modes may be affected. Note that this diagnostic is never
operational for BacNet Communication interface (BCIC) and only
operational with a LonTalk Communication interface (LCIC) if so
configured by the BAS or Tracer system.
Remote
Chiller Service
Recommended
Chiller
Warning
Latch
Service
Messages
Enabled
Chiller service interval time has elapsed. Chiller service is
recommended.
Remote
Compressor
Discharge
Refrigerant
Temperature
Sensor - xy
Cprsr Disch Rfgt
Temp Sensor -
xy
Disch Rfgt Temp
Sensor - xy
Cprsr
Immediate Latch
All
Bad Sensor or LLID
Remote
Condenser
Refrigerant
Pressure Sensor
Condenser Rfgt
Pressure Sensor
Cond Rfgt
Pressure Sensor
Circuit
Immediate Latch
All
Bad Sensor or LLID
Remote
Emergency Stop
Feedback Input
Emergency Stop
Chiller
Immediate Latch
All
EMERGENCY STOP FEEBBACK INPUT is open. An external interlock has
tripped. Time to trip from input opening to unit stop shall be 0.1 to 1.0
seconds.
Local
Evap Water
Pump 1 Svc
Recommended
Evap Water
Pump 1 Svc
Recom
Chiller
Info
Latch
Service
Messages
Enabled
Pump service recommended as service interval hours have elapsed. Remote
Evap Water
Pump 2 Svc
Recommended
Evap Water
Pump 2 Svc
Recom
Chiller
Info
Latch
Service
Messages
Enabled
Pump service recommended as service interval hours have elapsed. Remote
Evaporator
Approach Error
Circuit
Immediate Latch
Respective
circuit
running
The Evaporator approach temperature for the respective circuit (ELWT
– Evap Sat Temp Ckt x) is negative by more than 10°F for 1 minute
continuously while the circuit / compressor is operating. Either the Evap
Leaving Water Temp sensor or Evap Suction Rfgt Pressure Sensor Ckt
x is in error.
Remote