Controls
46
RTAF-SVX001A-EN
3. Touch Save.The Settings screen appears with only the
Security button visible. The Log in/Logout button is
gone.
To enable security:
1.
From the Settings screen, touch the Security button.
The Security screen appears (
Figure 37
).
2. Touch the Enable button.The button becomes shaded.
3. Touch Save. The Settings screen appears with a Log
out button, in addition to the Security button.
Logging In
There are two levels of security:
•
Security Level 1 allows users to change a limited group
of secure settings. The default security PIN is 1111.
•
Security Level 2 allows users to change all secure
settings. The default security PIN is 7123.
A technician must use theTracerTU service tool to define
a different PIN, or to recall a PIN that has been forgotten.
When defining a PIN in Tracer TU, the technician enters a
4-digit PIN that corresponds with the desired level of
security.
To log in:
1. Touch the Log in button. The Log in screen appears
(
Figure 38
).
2. Use the keypad to enter your PIN.
a. The PIN is a four-digit number, which was
configured for your system with the Tracer TU
service tool.
b. As you enter the number, the PIN remains hidden
by asterisks.
Note:
If you enter an invalid PIN, an error message
appears on the Log in screen.
3. Touch Save.
a. If you viewed the Log in screen from touching Log
in on the Settings screen, the Settings screen
appears with a Log out button on it.
b. If the Log in screen appeared when you tried to
change a setting, you return to that setting screen.
Note:
The PIN is valid until 30 minutes of inactivity
passes, or until you log out.
Logging Out
To log out:
1. Touch the Log out button. A confirmation screen
appears (
Figure 40
).
2. Touch Yes to confirm that you want to log out. The
Settings screen appears with a Log in button on it.
Figure 37.
Security screen - disable
Figure 38.
Security settings screen
Figure 39.
Log in screen
Figure 40.
Log out confirmation screen