Diagnostics
RTAF-SVX001A-EN
69
Starter Did
Not
Transition -
xy
Cprsr
Immediate Latch
On the first
check after
transition.
The Starter Module did not receive a transition complete signal in the
designated time from its command to transition. The Must Hold time
from the Starter Module transition command is 1 second. The Must Trip
time from the transition command is 6 seconds. Actual design is 2.5
seconds. This diagnostic is active only for Y-Delta, Auto-Transformer,
Primary Reactor, and X-Line Starters.
Local
Starter Dry
Run Test - xy
Circuit
Immediate Latch
Starter Dry Run
Mode
While in the Starter Dry Run Mode either 50% Line Voltage was sensed
at the Potential Transformers or 10% RLA Current was sensed at the
Current Transformers.
Local
Starter
Failed to
Arm/Start -
xy
Cprsr
Immediate Latch
All
Starter failed to arm or start within the allotted time (15 seconds).
Local
Starter Fault
Type I - xy
Cprsr
Immediate Latch
Starting - Y
Delta Starters
Only
This is a specific starter test where 1M(1K1) is closed first and a check
is made to ensure that there are no currents detected by the CT's. If
currents are detected when only 1M is closed first at start, then one of
the other contactors is shorted.
Local
Starter Fault
Type II - xy
Cprsr
Immediate Latch
Starting - All
types of
starters
a. This is a specific starter test where the Shorting Contactor (1K3) is
individually energized and a check is made to ensure that there are no
currents detected by the CT's. If current is detected when only S is
energized at Start, then 1M is shorted. b. This test in a. above applies
to all forms of starters (Note: It is understood that many starters do
not connect to the Shorting Contactor.).
Local
Starter Fault
Type III - xy
Cprsr
Immediate Latch
Starting
[Adaptive
Frequency
Starter Type]
As part of the normal start sequence to apply power to the compressor,
the Shorting Contactor (1K3) and then the Main Contactor (1K1) were
energized. 1.6 seconds later there were no currents detected by the
CT's for the last 1.2 Seconds on all three phases. The test above applies
to all forms of starters except Adaptive Frequency Drives.
Local
Starter
Module
Memory
Error Type 1
- xy
(Starter
Mem Err
Type 1 - xy)
Cprsr
Info
Latch
All
Checksum on RAM copy of the Starter LLID configuration failed.
Configuration recalled from EEPROM.
Local
Starter
Module
Memory
Error Type 2
- xy
(Starter
Mem Err
Type 2 - xy)
Cprsr
Immediate Latch
All
Checksum on EEPROM copy of the Starter LLID configuration failed.
Default configuration loaded into RAM and EEPROM.
Local
Transition
Complete
Input
Opened - xy
(Trnsn
Compl Input
Open xy)
Cprsr
Immediate Latch
All running
modes
The Transition Complete input was found to be opened with the
compressor motor running after a successful completion of transition.
This is active only for Y-Delta, Auto-Transformer, Primary Reactor, and
X-Line Starters. To prevent this diagnostic from occurring as the result
of a power loss to the contactors, the minimum time to trip must be
greater than the trip time for the power loss diagnostic.
Local
Transition
Complete
Input
Shorted - xy
(Trnsn
Compl Input
Short xy)
Cprsr
Immediate Latch
Pre-Start
The Transition Complete input was found to be shorted before the
compressor was started. This is active for all electromechanical
starters.
Local
Under
Voltage
Chiller Normal
NonLatch
Pre-Start and
Any Ckt(s)
Energzd
Nom. trip: 60 seconds at less than 87.5%, 2.8% at 200V 1.8% at
575V, Auto Reset at 90% or greater for 10 cont secs.
Remote
Table 26.
Starter diagnostics (continued)
Diagnostic
Name and
Source
Affects
Target Severity
Persistence
Active Modes
[Inactive
Modes]
Criteria
Reset
Level