Installation (Continued)
No System Control
Temperature Control Parameters
Each unit ordered with the “No Controls” option, requires a
field provided and field wired temperature controller. Single
refrigerant circuit units require a 2-step control device, and
dual refrigerant circuit units require a 4-step control device.
Each unit is shipped form the factory with internal “Fixed-
On” & “Fixed-Off” time delays wired into each step of cool-
ing. The “Fixed-Off” timers are 5 minutes each and they be-
gin timing when the circuit for that step of cooling is deacti-
vated. The “Fixed-On” timers are 3 minutes each and they
begin timing when the circuit for that step is activated.
Note: Units ordered with the “No Controls” option
can not be used with EVP Chiller applications.
Wire the controller in accordance with the field connection
diagram illustrated in Figure 3-11.
Figure 3-11A
Field Connection Diagram for RAUC-C80 “No System Controls” Application
Refer to Wiring Notes on
page 35
Diagram continued on
next page
Summary of Contents for RAUC-IOM-15
Page 8: ...8 Figure 3 2A RAUC C80 Unit Dimensional Data Recommended Clearances...
Page 9: ...9 Figure 3 2A Continued RAUC D10 Unit Dimensional Data Recommended Clearances...
Page 10: ...10 Figure 3 2A Continued RAUC D12 Unit Dimensional Data Recommended Clearances...
Page 11: ...11 Figure 3 2B EVPB C80 Evaporator Chiller Dimensions...
Page 12: ...12 Figure 3 2B Continued EVPB D10 Evaporator Chiller Dimensions...
Page 13: ...13 Figure 3 2B Continued EVPB D12 Evaporator Chiller Dimensions...
Page 14: ...14 Figure 3 2B Continued EVPB C80 through D12 Chill Water Pipe Stubout Dimensions...
Page 35: ...35 Installation Continued Field Connection Diagram Notes for all System Control Options...
Page 57: ...57 Figure 5 5 Typical Scroll Compressor Terminal Block System Start Up Continued...
Page 67: ...67...
Page 68: ...68...