15
Installation (Continued)
Table 3-1A
Typical Unit Weights & Point Loading Data
Unit
Fin
Operating
Unit Weight on Isolator @ Mounting Location
Size
Material
Weight
Location 1
2
3
4
5
6
7
8
C80
AL
5500
855
557
835
544
830
541
810
528
CU
6099
926
629
909
618
906
616
890
605
D10
AL
6472
1010
656
983
639
979
636
951
618
CU
7272
1104
752
1083
738
1080
736
1058
721
D12
AL
7000
1100
694
1075
678
1071
676
1046
660
CU
8199
1241
838
1225
827
1222
825
1206
815
Note:
1. Mounting locations correlate with those shown in point loading illustration.
Table 3-1B
Typical EVP Chiller Weights & General Data
Chiller
Shipping Operating
No. of Ref.
Capacity
Refrigerant
Tube Pull
Size
Weight
Weight
Circuits
(Gallons)
Charge (Lbs.)*
(inches)**
80 Ton
875
1,205
2
43.1
26.5
95
100 Ton
960
1,230
2
35.0
33.4
95
120 Ton
1,150
1,535
2
47.9
40.4
95
* - Refrigerant change is approximate and for the evaporator chiller only.
** - Tube Pull given is the length of the evaporator.
Figure 3-3
Rigging and Center-of-Gravity Data
Location of Center of
Shipping
Gravity =
Unit
Weight
X
Z
Size
(Max. Lbs)
In
mm
In
mm
C80
5995
79.1
2009
34.5
876.3
D10
7160
104.2
2647
34.6
878.8
D12
8052
104.7
2659
34.4
873.8
L I F T I N G A N D M O V I N G I N S T R U C T I O N S !
DO NOT USE CABLES (CHAINS OR SLINGS) EXCEPT AS
SHOWN. OTHER LIFTING ARRANGEMENTS MAY CAUSE
EQUIPMENT DAMAGE OR SERIOUS PERSONAL INJURY.
EACH OF THE CABLES (CHAINS OR SLINGS) USED TO LIFT
UNIT MUST BE CAPABLE OF SUPPORTING THE ENTIRE
WEIGHT OF THE UNIT.
LIFTING CHAINS (CABLES OR SLINGS) MAY NOT BE THE
SAME LENGTH. ADJUST AS NECESSARY FOR EVEN
LEVEL LIFT.
USE SPREADER BARS AS SHOWN IN DIAGRAM. REFER
TO INSTALLATION MANUAL OR NAMEPLATE FOR UNIT
WEIGHT. REFER TO INSTALLATION INSTRUCTIONS
LOCATED INSIDE CONTROL PANEL FOR FURTHER
RIGGING INFORMATION.
Summary of Contents for RAUC-IOM-15
Page 8: ...8 Figure 3 2A RAUC C80 Unit Dimensional Data Recommended Clearances...
Page 9: ...9 Figure 3 2A Continued RAUC D10 Unit Dimensional Data Recommended Clearances...
Page 10: ...10 Figure 3 2A Continued RAUC D12 Unit Dimensional Data Recommended Clearances...
Page 11: ...11 Figure 3 2B EVPB C80 Evaporator Chiller Dimensions...
Page 12: ...12 Figure 3 2B Continued EVPB D10 Evaporator Chiller Dimensions...
Page 13: ...13 Figure 3 2B Continued EVPB D12 Evaporator Chiller Dimensions...
Page 14: ...14 Figure 3 2B Continued EVPB C80 through D12 Chill Water Pipe Stubout Dimensions...
Page 35: ...35 Installation Continued Field Connection Diagram Notes for all System Control Options...
Page 57: ...57 Figure 5 5 Typical Scroll Compressor Terminal Block System Start Up Continued...
Page 67: ...67...
Page 68: ...68...