SS-SVX09A-EN
83
System Start-Up
Sequence of Operation
VAV W7100A Discharge Air Controller (7U11)
The discharge air controller used in Variable Air Volume applications is a Honeywell W7100A. This
microprocessor controller is designed to maintain an average discharge air (D/A) temperature by:
1.
monitoring the discharge air temperature sensor; and
2. modulating economizer dampers and sequencing stages of mechanical cooling “On” or “Off”,
as required.
The W7100A receives analog input from the discharge air sensor mounted in the supply duct every
2 to 3 seconds by pulsing DC current across the sensor, then “reading” the voltage potential across
this thermistor.
If the comparison between the setpoint and the actual discharge air temperature indicates that
cooling is required, the W7100A attempts to satisfy the load by modulating the economizer open
(if applicable).
Economizer Cycle
The economizer is only allowed to function if the ambient conditions are below the setpoint of the
enthalpy switch.
If the ambient air conditions are above the enthalpy setpoint, the W7100A will open the Fresh Air
dampers to the minimum setpoint position.
To take full advantage of the “free cooling” provided by the economizer, the W7100A “resets” the
discharge air setpoint. The amount of “reset” between the actual discharge air setpoint and the
economizer control point is equal to 1/2 of the W7100’s control band setpoint.
Example:
With a typical control band setting of 6oF, the amount of discharge air “reset” is 3ºF (1/
2 of the control band setpoint). Therefore, if the discharge air setpoint is 55ºF, the economizer
control point is 52ºF (i.e., 55ºF - 3ºF).
A second economizer “algorithm” within the W7100A is the response time of the controller. The
greater the amount of deviation between the discharge air temperature and the economizer control
point, i.e., as the temperature strays further from the control point, the response time becomes
faster; and, as the discharge air temperature approaches the control point, the response time
becomes slower.
When the discharge air temperature is within the “Deadband” (± 1.5ºF of the economizer control
point); the W7100A maintains the economizer’s present position.
When the economizer can not handle the cooling requirement or when the outdoor ambient
conditions are unsuitable for “economizing”, the W7100A activates the unit’s mechanical cooling
section.
Note:
As long as ambient conditions are suitable for economizing, the economizer works in
conjunction with the mechanical cooling operation.
The control algorithm used by the W7100A to add stages of cooling is illustrated in
Figure 41
. When
the discharge air temperature drifts above the setpoint, “Region 1”, a stage of mechanical cooling
is added based on time and the amount of deviation from setpoint. If the discharge air temperature
remains above the setpoint, the W7100A energizes additional stages of mechanical cooling.
If the operating cooling stage is capable of satisfying the cooling requirement, as the discharge air
temperature falls below the setpoint for a sufficient period of time, the W7100A turns the stages
of mechanical cooling “Off”, “Region 3”.
The W7100A determines the length of the time before stages of mechanical cooling are turned
“On” and “Off”. When the system is operating within the control band, the delay is longest at
setpoint, and decreases to a minimum of 4 minutes when the discharge air temperature exceeds
the upper or lower limit of the control band. Refer to the illustration in
Figure 41
.
Summary of Contents for RAUC-C20
Page 10: ...10 SS SVX09A EN Installation Figure 3 RAUC C20 Unit Dimensional Data Recommended Clearances...
Page 11: ...SS SVX09A EN 11 Installation Figure 4 RAUC C25 Unit Dimensional Data Recommended Clearances...
Page 12: ...12 SS SVX09A EN Installation Figure 5 RAUC C30 Unit Dimensional Data Recommended Clearances...
Page 13: ...SS SVX09A EN 13 Installation Figure 6 RAUC C40 Unit Dimensional Data Recommended Clearances...
Page 14: ...14 SS SVX09A EN Installation Figure 7 RAUC C50 Unit Dimensional Data Recommended Clearances...
Page 15: ...SS SVX09A EN 15 Installation Figure 8 RAUC C60 Unit Dimensional Data Recommended Clearances...
Page 55: ...SS SVX09A EN 55 Installation Field Connection Diagram Notes for all System Control Options...
Page 67: ...SS SVX09A EN 67 Installation Figure 33 6RT1 Discharge Air Sensor Assembly...
Page 96: ...96 SS SVX09A EN System Start Up Figure 47 20 Ton Pressure Curve...
Page 97: ...SS SVX09A EN 97 System Start Up Figure 48 25 Ton Pressure Curve...
Page 98: ...98 SS SVX09A EN System Start Up Figure 49 30Ton Pressure Curve...
Page 99: ...SS SVX09A EN 99 System Start Up Figure 50 40 Ton Pressure Curve per Circuit...
Page 100: ...100 SS SVX09A EN System Start Up Figure 51 50 Ton Pressure Curve per Circuit...
Page 101: ...SS SVX09A EN 101 System Start Up Figure 52 60 Ton Pressure Curve per Circuit...