80
SS-SVX09A-EN
System Pre-Start Procedures
Discharge Air Sensor Checkout (Honeywell 6RT1)
WARNING
Hazardous Voltage!
Disconnect all electric power, including remote disconnects before servicing. Follow proper
lockout/tagout procedures to ensure the power can not be inadvertently energized. Failure to
disconnect power before servicing could result in death or serious injury.
1.
Turn the control circuit switch 1S2, in the unit control panel, to the “OFF” position.
2. At the Master Energy Controller, disconnect the wire connected to Terminal T1. Use a digital
ohmmeter to measure the resistance between Terminal T and the wire removed from Terminal
T1.
3. Use the conversion chart in
Figure 37
to convert the measured resistance to an equivalent
temperature.
4. Measure the actual temperature at the sensor location. If the measured resistance in step 2 is
not within ± 10.0 ohms of the actual temperature, the 6RT1 is out of range; replace it.
Note:
Before condemning the sensor, verify that the connecting cable resistance is not excessive.
Refer to the “Field Installed Control Wiring” section.
5. Make all necessary repairs and reconnect the duct sensor lead to terminal T1 on the controller.
6. Turn switches 1S2, 5S1, & 5S2 to the “ON” position to restore power to the control system.
Table 12. Zone Thermostat (6U37) “Voltage Output” ramps
1U11
Function
Nominal Operating Points and Throtting Ranges
Measured
between
these 1U11
Terminals
Pull-In
Voltage*
Drop-Out
Voltage
Throtting
Range
HEAT 1
4.63 VDC
4.0 VDC
HEAT 2
5.88 VDC
5.25 VDC
Terminal 5 (heating)
&
Terminal 1 (common)
HEAT 3
7.13 VDC
6.50 VDC
HEAT 4
8.38 VDC
7.75 VDC
COOL 1
4.58 - 5.42 VDC
3.44 - 4.56 VDC
Terminal 4 (cooling)
&
Terminal 1 (common)
COOL 2
5.43 - 6.34 VDC
4.69 - 5.81 VDC
COOL 3
6.63 - 7.63 VDC
5.90 - 7.10 VDC
COOL 4
7.84 - 8.92 VDC
7.11 - 8.39 VDC
Economizer
2.75 - 4.00 VDC
* "Pull-In" and "Drop-Out" valves are ± 0.25 VDC
** If Applicable
Summary of Contents for RAUC-C20
Page 10: ...10 SS SVX09A EN Installation Figure 3 RAUC C20 Unit Dimensional Data Recommended Clearances...
Page 11: ...SS SVX09A EN 11 Installation Figure 4 RAUC C25 Unit Dimensional Data Recommended Clearances...
Page 12: ...12 SS SVX09A EN Installation Figure 5 RAUC C30 Unit Dimensional Data Recommended Clearances...
Page 13: ...SS SVX09A EN 13 Installation Figure 6 RAUC C40 Unit Dimensional Data Recommended Clearances...
Page 14: ...14 SS SVX09A EN Installation Figure 7 RAUC C50 Unit Dimensional Data Recommended Clearances...
Page 15: ...SS SVX09A EN 15 Installation Figure 8 RAUC C60 Unit Dimensional Data Recommended Clearances...
Page 55: ...SS SVX09A EN 55 Installation Field Connection Diagram Notes for all System Control Options...
Page 67: ...SS SVX09A EN 67 Installation Figure 33 6RT1 Discharge Air Sensor Assembly...
Page 96: ...96 SS SVX09A EN System Start Up Figure 47 20 Ton Pressure Curve...
Page 97: ...SS SVX09A EN 97 System Start Up Figure 48 25 Ton Pressure Curve...
Page 98: ...98 SS SVX09A EN System Start Up Figure 49 30Ton Pressure Curve...
Page 99: ...SS SVX09A EN 99 System Start Up Figure 50 40 Ton Pressure Curve per Circuit...
Page 100: ...100 SS SVX09A EN System Start Up Figure 51 50 Ton Pressure Curve per Circuit...
Page 101: ...SS SVX09A EN 101 System Start Up Figure 52 60 Ton Pressure Curve per Circuit...