SS-SVX09A-EN
107
Service & Maintenance
[ ] Verify that all wire terminal connections are tight.
[ ] Generally inspect the unit for unusual conditions (e.g., loose access panels, leaking piping
connections, etc.)
[ ] Make sure that all retaining screws are reinstalled in the unit access panels once these checks
are complete.
Condensing Unit
WARNING
Rotating Components!
Disconnect all electric power, including remote disconnects before verifying proper fan rotation.
Follow proper lockout/tagout procedures to ensure the power can not be inadvertently
energized. Failure to disconnect power could result in fan turning on unexpectedly resulting in
death or serious injury.
[ ] Manually rotate the condenser fans to ensure free movement and check motor bearings for wear.
Verify that all of the fan mounting hardware is tight.
[ ] Verify that all wire terminal connections are tight.
[ ] Inspect the condenser coils for dirt and foreign debris. If the coils appear dirty, clean them
according to the instructions described in the “Coil Cleaning” section.
[ ] Inspect the compressor and condenser fan motor contactors. If the contacts appear severely
burned or pitted, replace the contactor. Do not clean the contacts.
[ ] Check the compressor oil level. (Compressors "Off")
Coil Cleaning
Regular coil maintenance, including annual cleaning, enhances the unit’s operating efficiency by
minimizing:
compressor head pressure and amperage draw;
evaporator water carryover;
fan brake horsepower, due to increase static pressure losses;
airflow reduction.
At least once each year, or more often if the unit is located in a “dirty” environment, clean the
evaporator and condenser coils using the instructions outlined below. Be sure to follow these
instructions as closely as possible to avoid damaging the coils.
To clean refrigerant coils, use a soft brush and a sprayer (either a garden pump-up type or a high-
pressure sprayer). A high-quality detergent is also required; suggested brands include “SPREX
A.C.”, “OAKITE 161”, “OAKITE 166” and “COILOX”. If the detergent selected is strongly alkaline (ph
value exceeds 8.5), add an inhibitor.
1.
Remove enough panels from the unit to gain access to the coil.
2. Protect all electrical devices such as motors and controllers from any over spray.
3. Straighten any bent coil fins with a fin comb.
4. Mix the detergent with water according to the manufacturer’s instructions. If desired, heat the
solution to 150oF maximum to improve its cleansing capability.
Summary of Contents for RAUC-C20
Page 10: ...10 SS SVX09A EN Installation Figure 3 RAUC C20 Unit Dimensional Data Recommended Clearances...
Page 11: ...SS SVX09A EN 11 Installation Figure 4 RAUC C25 Unit Dimensional Data Recommended Clearances...
Page 12: ...12 SS SVX09A EN Installation Figure 5 RAUC C30 Unit Dimensional Data Recommended Clearances...
Page 13: ...SS SVX09A EN 13 Installation Figure 6 RAUC C40 Unit Dimensional Data Recommended Clearances...
Page 14: ...14 SS SVX09A EN Installation Figure 7 RAUC C50 Unit Dimensional Data Recommended Clearances...
Page 15: ...SS SVX09A EN 15 Installation Figure 8 RAUC C60 Unit Dimensional Data Recommended Clearances...
Page 55: ...SS SVX09A EN 55 Installation Field Connection Diagram Notes for all System Control Options...
Page 67: ...SS SVX09A EN 67 Installation Figure 33 6RT1 Discharge Air Sensor Assembly...
Page 96: ...96 SS SVX09A EN System Start Up Figure 47 20 Ton Pressure Curve...
Page 97: ...SS SVX09A EN 97 System Start Up Figure 48 25 Ton Pressure Curve...
Page 98: ...98 SS SVX09A EN System Start Up Figure 49 30Ton Pressure Curve...
Page 99: ...SS SVX09A EN 99 System Start Up Figure 50 40 Ton Pressure Curve per Circuit...
Page 100: ...100 SS SVX09A EN System Start Up Figure 51 50 Ton Pressure Curve per Circuit...
Page 101: ...SS SVX09A EN 101 System Start Up Figure 52 60 Ton Pressure Curve per Circuit...