Installation
Constant Volume Control (Honeywell 973)
The descriptions of the following basic input devices used with the Honeywell 973 Master Energy
Controller (MEC) are to acquaint the operator with their function as they interface with the
controller. Refer to the field connection diagram in
Figure 32
for the specific component
connections at the unit’s control panel.
Electronic Zone Thermostat (Honeywell T7067)
Each unit ordered with constant volume controls (digit 9 in the model number) is shipped with a
Honeywell T7067 electronic zone thermostat. A Honeywell switching subbase (Q667) is also
included. The switching subbase allows the operator to select the “System Mode” of operation, i.e.,
Cool, Heat, Auto, or Off and the “Fan Mode” of operation, i.e., On or Auto.
Note:
As long as the status of the system is in an occupied mode, the supply fan will operate
continuously. The fan will only cycle in the “Auto” mode during unoccupied periods.
The zone thermostat should be located in an area with good air circulation to enhance zone
temperature averaging. Position the thermostat about 54" above the floor in a frequently occupied
area.
Do not mount the thermostat where its sensing element may be affected by:
a. Drafts or “dead” spots behind doors or in corners;
b. Hot or cold air from ducts;
c. Radiant heat from the sun, or from appliances;
d. Concealed pipes and chimneys;
e. Vibrating surfaces; or
f. Unconditioned areas behind the thermostat (e.g., outside walls).
Mount the thermostat subbase on either a standard 2" X 4" handy box, a comparable European
outlet box, or on any nonconductive flat surface. Refer to the illustration in
Figure 30
for mounting
details.
Note:
Specific installation instructions are packaged with each thermostat and subbase. For
subbase and thermostat terminal identification, refer to
Figure 31
.
Thermostat Checkout
Once the subbase is mounted, before connecting any wiring, use an ohm meter and complete the
continuity checks listed in
Table 11
.
Thermostat Wiring
WARNING
Hazardous Voltage!
Disconnect all electric power, including remote disconnects before servicing. Follow proper
lockout/tagout procedures to ensure the power can not be inadvertently energized. Failure to
disconnect power before servicing could result in death or serious injury.
Before installing any connecting wiring, refer to
Figure 3
to
Figure 8
for the electrical access
locations provided on the unit. Wire the thermostat in accordance with the field connection
diagram in
Figure 32
.
Summary of Contents for RAUC-C20
Page 10: ...10 SS SVX09A EN Installation Figure 3 RAUC C20 Unit Dimensional Data Recommended Clearances...
Page 11: ...SS SVX09A EN 11 Installation Figure 4 RAUC C25 Unit Dimensional Data Recommended Clearances...
Page 12: ...12 SS SVX09A EN Installation Figure 5 RAUC C30 Unit Dimensional Data Recommended Clearances...
Page 13: ...SS SVX09A EN 13 Installation Figure 6 RAUC C40 Unit Dimensional Data Recommended Clearances...
Page 14: ...14 SS SVX09A EN Installation Figure 7 RAUC C50 Unit Dimensional Data Recommended Clearances...
Page 15: ...SS SVX09A EN 15 Installation Figure 8 RAUC C60 Unit Dimensional Data Recommended Clearances...
Page 55: ...SS SVX09A EN 55 Installation Field Connection Diagram Notes for all System Control Options...
Page 67: ...SS SVX09A EN 67 Installation Figure 33 6RT1 Discharge Air Sensor Assembly...
Page 96: ...96 SS SVX09A EN System Start Up Figure 47 20 Ton Pressure Curve...
Page 97: ...SS SVX09A EN 97 System Start Up Figure 48 25 Ton Pressure Curve...
Page 98: ...98 SS SVX09A EN System Start Up Figure 49 30Ton Pressure Curve...
Page 99: ...SS SVX09A EN 99 System Start Up Figure 50 40 Ton Pressure Curve per Circuit...
Page 100: ...100 SS SVX09A EN System Start Up Figure 51 50 Ton Pressure Curve per Circuit...
Page 101: ...SS SVX09A EN 101 System Start Up Figure 52 60 Ton Pressure Curve per Circuit...