102
SS-SVX09A-EN
System Start-Up
Final System Setup
After completing the Pre-start and Start-up procedures outlined in the previous sections, perform
these final checks before leaving the unit:
[ ] Turn the 115 volt control circuit switch 1S2 “Off”.
[ ] Program the Night Setback (NSB) panel (if applicable) for proper unoccupied operation. Refer
to the programming instructions for the specific panel.
[ ] Verify that the “System” selection switch and the “Fan Mode” selection switch at the Remote
panel is set correctly.
[ ] Verify that the “System” control switch for the supply fan or the chilled water pump is “On”.
[ ] Set the correct “Operating Temperature” for the system at the system controller. Refer to
Figure 17
for the recommended control set points for the appropriate control option.
[ ] Turn the 115 volt control circuit switch 1S2 “On”. The system will start automatically once a
request for cooling has been given.
[ ] Verify that all exterior panels and the control panel doors are secured in place.
Table 17. Recommended Operating Setpoints
Control
Control Setting
Recommended Setting
Discharge Air
Controller
(VAV units only)
Supply Air Setpoint
Set at design discharge (supply) air temperature;
minimum setting = 55
o
F
Reset Setpoint
Set at maximum amount of allowable reset for supply
air setpoint.
Control Band
Set at 6
o
F Minimum Setpoint
Chiller Control
(EVP units only)
Freezestat
Leaving Fluid Setpoint
Set at design leaving chilled water temperature
(typically) 44
o
F
Reset Setpoint
Set at maximum amount of allowable reset for
leaving fluid setpoint.
Control Band
Set at 6
o
F Minimum Setpoint
Low Limit Solution Temperature
Set at 5
o
F Minimum above the Chilled Solution
Freeze Temperature
Zone Thermostat (CV units
only)
Zone Setpoint
Set at desired space temperature.
Note:
"No Controls" Units See System Engineer
Summary of Contents for RAUC-C20
Page 10: ...10 SS SVX09A EN Installation Figure 3 RAUC C20 Unit Dimensional Data Recommended Clearances...
Page 11: ...SS SVX09A EN 11 Installation Figure 4 RAUC C25 Unit Dimensional Data Recommended Clearances...
Page 12: ...12 SS SVX09A EN Installation Figure 5 RAUC C30 Unit Dimensional Data Recommended Clearances...
Page 13: ...SS SVX09A EN 13 Installation Figure 6 RAUC C40 Unit Dimensional Data Recommended Clearances...
Page 14: ...14 SS SVX09A EN Installation Figure 7 RAUC C50 Unit Dimensional Data Recommended Clearances...
Page 15: ...SS SVX09A EN 15 Installation Figure 8 RAUC C60 Unit Dimensional Data Recommended Clearances...
Page 55: ...SS SVX09A EN 55 Installation Field Connection Diagram Notes for all System Control Options...
Page 67: ...SS SVX09A EN 67 Installation Figure 33 6RT1 Discharge Air Sensor Assembly...
Page 96: ...96 SS SVX09A EN System Start Up Figure 47 20 Ton Pressure Curve...
Page 97: ...SS SVX09A EN 97 System Start Up Figure 48 25 Ton Pressure Curve...
Page 98: ...98 SS SVX09A EN System Start Up Figure 49 30Ton Pressure Curve...
Page 99: ...SS SVX09A EN 99 System Start Up Figure 50 40 Ton Pressure Curve per Circuit...
Page 100: ...100 SS SVX09A EN System Start Up Figure 51 50 Ton Pressure Curve per Circuit...
Page 101: ...SS SVX09A EN 101 System Start Up Figure 52 60 Ton Pressure Curve per Circuit...