Comm Loss: Outdoor Air
Temperature
Chiller
Warning
and Special
Action
Latch
All
"Continual loss of communication between the MP
and the Functional ID has occurred for a 30 second
period. Note that if this diagnostic occurs, Chiller
shall remove any OA Chilled Water Reset, if it was in
effect and if Tracer OA was unavailable. Apply slew
rates per Chilled Water Reset spec"
Remote
Comm Loss: Primary Oil
Line Solenoid Valve
Chiller
Normal
Latch
All
Continual loss of communication between the MP and
the Functional ID has occurred for a 30 second
period.
Remote
Comm Loss: Refrigerant
Monitor Input
Chiller
Warning
Latch
All
Continual loss of communication between the MP and
the Functional ID has occurred for a 30 second
period.
Remote
Comm Loss: Slide Valve
Load
Chiller
Normal
Latch
All
Continual loss of communication between the MP and
the Functional ID has occurred for a 30 second
period.
Remote
Comm Loss: Slide Valve
Unload
Chiller
Normal
Latch
All
Continual loss of communication between the MP and
the Functional ID has occurred for a 30 second
period.
Remote
Comm Loss: SSS/AFD Fault Chiller
Warning
Latch
All
Continual loss of communication between the MP and
the Functional ID has occurred for a 30 second
period.
Remote
Comm Loss: Starter
Chiller
Immediate Latch
All
Continual loss of communication between the MP and
the Functional ID has occurred for a 30 second
period.
Local
Comm Loss: Winding Temp
1
Chiller
Normal
Latch
All
Continual loss of communication between the MP and
the Functional ID has occurred for a 30 second period
Remote
Comm Loss: Winding Temp
2
Chiller
Normal
Latch
All
Continual loss of communication between the MP and
the Functional ID has occurred for a 30 second period
Remote
Starter Comm Loss: Main
Processor
Chiller
Immediate Latch
All
Starter has had a loss of communication with the MP
for a 15 second period.
Local
Table 27. Communication diagnostics (continued)
Diagnostic Name
Affects
Severity Persistence
Active
Modes
[Inactive
Modes]
Criteria
Reset
Level
Summary of Contents for Optimus RTHD
Page 27: ...Installation Mechanical RTHD SVX01K EN 27...
Page 28: ...Installation Mechanical 28 RTHD SVX01K EN...
Page 29: ...Installation Mechanical RTHD SVX01K EN 29...
Page 54: ...Controls 54 RTHD SVX01K EN Figure 23 Tracer TU...
Page 88: ...Log and Check Sheets 88 RTHD SVX01K EN Page Left Intentionally Blank...
Page 95: ...Notes RTAF SVX001K EN 95...