Diagnostics
76
RTHD-SVX01K-EN
Main Processor Diagnostics
AFD Output
Phase Loss
Chiller
Immediate Latching
Compressor
Running
Drive sensed an output phase is missing. Output phase
loss is defined as greater than 15% output current
imbalance for more than 5.0 seconds.
Local
AFD Rated
Current out of
Range
Chiller
Warning
Latching
All
The configuration motor rated current bigger than AFD
rated current
Local
Comm Loss:
Adaptive
Frequency Drive
Chiller
Normal
Non-Latching All
Continual loss of communication between the MP and
the Functional ID has occurred for a 6-10 second
period.
Local
High Pressure
Cutout
Chiller
Immediate Latching
All
The high pressure hardware switch was tripped.
Table 25. Local communication drive diagnostics (continued)
Diagnostic
Name and
Source
Affects
Target Severity
Persistence
Active Modes
[Inactive
Modes]
Criteria
Reset
Level
Table 26. Main processor diagnostics
Diagnostic
Name and
Source
Affects
Target Severity
Persistence
Active Modes
[Inactive
Modes]
Criteria
Reset
Level
AFD Output
Power Input
Chiller
Warning
NonLatch
All
"Out-Of-Range Low or Hi or bad LLID, set diagnostic, This
Info diagnostic will automatically reset if the input returns
to the normal range."
Remote
Compressor
Discharge
Temperature
Sensor
Chiller
Immediate Latch
All
Bad Sensor or LLID
Remote
Condenser Diff
Water Pressure
Xdcr
Chiller
Warning
Latching
All
Defective Sensor or LLID
Display invalid value.
Flow calculation shall be disabled.
Remote
Condenser
Entering Water
Temp Sensor
Chiller
Warning
and Special
Action
Latch
All
Bad Sensor or LLID. If chiller running, and condenser water
regulating valve option installed, force valve to 100% flow.
Remote
Condenser
Leaving Water
Temp Sensor
Chiller
Warning
Latch
All
Bad Sensor or LLID
Remote
Condenser Rfgt
Pressure
Transducer
Chiller
Normal
Latch
All
Bad Sensor or LLID
Remote
Condenser
Water Flow Lost
Chiller
Immediate NonLatch
Start and All Run
Modes
The condenser water flow proof input was open for more
than 6 contiguous seconds after flow had been proven.
This diagnostic is automatically cleared once the
compressor is stopped by a fixed time out of 7 sec. The
Cond Pump shall be commanded off but the Evap pump
command will not be effected.
Remote
Condenser
Water Flow
Overdue
Chiller
Normal
NonLatch
Estab Cond Water
Flow - or for 1st 10
sec after Ignore DP
setting is reached if
Cond Wtr Flow
Proving Ignore is
enabled
Condenser water flow was not proven within 20 minutes of
the condenser pump relay being energized. The Cond
Pump shall be commanded off. Diagnostic is reset with
return of flow (although only possible with external control
of pump). This diagnostic may also occur if Cond Wtr Flow
Proving Ignore is enabled, and flow is not immediately
proven as the Ignore DP setting is reached."
Remote
Economizer
Pressure Sensor
Chiller
Normal
Latch
All
Bad Sensor or LLID
Remote
Economizer
Temperature
Sensor
Chiller
Normal
Latch
All
Bad Sensor or LLID
Remote
Emergency Stop Chiller
Immediate Latch
All
EMERGENCY STOP input is open. An external interlock has
tripped. Time to trip from input opening to unit stop shall
be 0.1 to 1.0 seconds.
Local
Summary of Contents for Optimus RTHD
Page 27: ...Installation Mechanical RTHD SVX01K EN 27...
Page 28: ...Installation Mechanical 28 RTHD SVX01K EN...
Page 29: ...Installation Mechanical RTHD SVX01K EN 29...
Page 54: ...Controls 54 RTHD SVX01K EN Figure 23 Tracer TU...
Page 88: ...Log and Check Sheets 88 RTHD SVX01K EN Page Left Intentionally Blank...
Page 95: ...Notes RTAF SVX001K EN 95...