Diagnostics
82
RTHD-SVX01K-EN
Communication Diagnostics
Notes:
•
The following communication loss diagnostics will not
occur unless that input or output is required to be
present by the particular configuration and installed
options for the chiller.
•
Communication diagnostics (with the exception of
“Excessive Loss of Comm” are named by the
Functional Name of the input or output that is no
longer being heard from by the Main Processor. Many
LLIDs, such as the Quad Relay LLID, have more than
one functional output associated with it. A comm loss
with such a multiple function board, will generate
multiple diagnostics. Refer to the Chiller's wiring
diagrams to relate the occurrence of multiple
communication diagnostics back to the physical LLID
boards that they have been assigned to (bound).
Table 27. Communication diagnostics
Diagnostic Name
Affects
Severity Persistence
Active
Modes
[Inactive
Modes]
Criteria
Reset
Level
Comm Loss: Adaptive
Frequency Drive
Chiller
Immediate NonLatching
All
Continual loss of communication between the MP and
the Functional ID has occurred for a 35-40 second
period. Flow calculation shall be disabled.
Remote
Comm Loss: AFD Output
Power Input
Chiller
Immediate Latch
All
Continual loss of communication between the MP and
the Functional ID has occurred for a 30 second
period.
Remote
Comm Loss: AFD Speed
Signal Output
Chiller
Immediate Latch
All
Continual loss of communication between the MP and
the Functional ID has occurred for a 30 second
period.
Remote
Comm Loss: Compressor %
RLA Output
Chiller
Warning
Latch
All
Continual loss of communication between the MP and
the Functional ID has occurred for a 30 second
period.
Remote
Comm Loss: Cond Diff
Water Pressure
Chiller
Warning
Latching
All
Continual loss of communication between the MP and
the Functional ID has occurred for a 35-40 second
period. Flow calculation shall be disabled.
Remote
Comm Loss: Cond Head
Press Cntrl Output
Chiller
Immediate Latch
All
Continual loss of communication between the MP and
the Functional ID has occurred for a 30 second
period.
Remote
Comm Loss: Cond Rfgt
Pressure Output
Chiller
Normal
Latch
All
Continual loss of communication between the MP and
the Functional ID has occurred for a 30 second
period.
Remote
Comm Loss: Condenser
Entering Water Temp
Chiller
Warning
and Special
Action
Latch
All
"Continual loss of communication between the MP
and the Functional ID has occurred for a 30 second
period. If chiller running, and condenser water
regulating valve option installed, force valve to 100%
flow."
Remote
Comm Loss: Condenser
Leaving Water Temp
Chiller
Info
Latch
All
Continual loss of communication between the MP and
the Functional ID has occurred for a 30 second
period.
Remote
Comm Loss: Condenser
Rfgt Pressure
Chiller
Normal
Latch
All
Continual loss of communication between the MP and
the Functional ID has occurred for a 30 second
period.
Remote
Comm Loss: Condenser
Water Flow Switch
Chiller
Immediate Latch
All
Continual loss of communication between the MP and
the Functional ID has occurred for a 30 second
period.
Remote
Comm Loss: Condenser
Water Pump Relay
Chiller
Warning
Latch
All
Continual loss of communication between the MP and
the Functional ID has occurred for a 30 second
period.
Remote
Comm Loss: Cprsr
Discharge Rfgt Temp
Chiller
Immediate Latch
All
Continual loss of communication between the MP and
the Functional ID has occurred for a 30 second
period.
Remote
Comm Loss: Economizer
Bypass Valve
Chiller
Normal
Latch
All
Continual loss of communication between the MP and
the Functional ID has occurred for a 30 second period
Remote
Comm Loss: Economizer
Pressure
Chiller
Normal
Latch
All
Continual loss of communication between the MP and
the Functional ID has occurred for a 30 second
period.
Remote
Summary of Contents for Optimus RTHD
Page 27: ...Installation Mechanical RTHD SVX01K EN 27...
Page 28: ...Installation Mechanical 28 RTHD SVX01K EN...
Page 29: ...Installation Mechanical RTHD SVX01K EN 29...
Page 54: ...Controls 54 RTHD SVX01K EN Figure 23 Tracer TU...
Page 88: ...Log and Check Sheets 88 RTHD SVX01K EN Page Left Intentionally Blank...
Page 95: ...Notes RTAF SVX001K EN 95...