Installation Electrical
40
RTHD-SVX01K-EN
Electrical Data Table Information
Compressor motor electrical data is provided in
for each compressor size. Rated load
amperes (RLA), locked rotor wye amperes (LRA) and
expected inrush for the Wye-delta configurations are
shown.
Although the terms “LRA” and “expected inrush” are
often used interchangeably, the distinction applied here is
that LRA is the rated inrush for the motor, but expected
inrush is that allowed by the starter, based on the specific
configuration. Selecting starters in the Wye-delta
configuration lowers expected inrush vs. the Delta (or
“across-the- line”) configuration.
The RLA is based on the motor’s performance when
reaching full rated horsepower. The kW rating of the motor
will equal or exceed the kW requirement indicated by the
TOPSS™ selection program at design conditions. If motor
kW draw at design conditions is less than the kW rating of
the motor, the RLA at design conditions is determined by
multiplying the motor RLA (at the desired voltage) by this
ratio: design kW/ motor kW rating. This calculation is
performed within the computer selection program,
making RLA available as part of the design predictions.
Predicted values include power factor variation from point
to point.
Optimus™ chillers are designed to operate satisfactorily
over a utilization range of ±10 percent of the standard
design voltages: (a) 200V, 230V, 380V, 460V, and 575V for
60 Hertz, 3- phase, and (b) 380V, 400V, 415V for 50 Hertz,
3-phase.
Units with AFD Option
Installer-Supplied Components
Customer wiring interface connections are shown in the
electrical schematics and connection diagrams that are
shipped with the unit. The installer must provide the
following components if not ordered with the unit:
•
Power supply wiring (in conduit) for all field-wired
connections.
•
All control (interconnecting) wiring (in conduit) for
field supplied devices.
•
Fused-disconnect switches or circuit breakers.
Table 12. Compressor motor electrical data (50 Hz) —
standard units (wye-delta starter)
Compressor
Code
(a)
(a) Unit model number digits 6 & 7.
Voltage
(b)
(b) Voltage utilization ranges: 380V (342-418), 400V (360-440), 415V
(374-457).
Max kW
RLA @
Max
kW
(c)
(c) The RLA @ Max k@ is based on the performance of the motor developing
full rated horsepower.
LRA
(Wye)
LRA
(Delta)
B1, B2
380
139
233
391
1229
400
145
233
412
1296
415
148
233
428
1348
C1, C2
380
201
349
456
1414
400
209
349
480
1488
415
213
349
498
1544
D1, D2, D3
380
271
455
711
2303
400
280
455
748
2424
415
284
455
776
2515
E3
380
288
488
711
2303
400
301
488
748
2424
415
306
488
776
2515
Table 13. Electrical data — units with AFD
Voltage
Applied Range
(Model Number
digits 56-58)
Estimated Power
Loss (W)
575V 60 Hz
0 - 126
1739
127 - 150
2099
151 - 185
2646
186 - 234
3071
235 - 279
3719
280 - 316
4460
317 - 366
5023
460V 60 Hz
0 - 176
2257
177 - 223
2719
224 - 280
3622
281 - 335
3561
336 - 411
4558
412 - 455
5703
380V 60 Hz
0 - 197
2555
198 - 241
2949
242 - 292
3764
293 - 367
4109
368 - 446
5129
447 - 549
6663
380V 50 Hz
400V 50 Hz
415V 50 Hz
0 - 197
2555
198 - 241
2949
242 - 292
3764
293 - 367
4109
368 - 446
5129
447 - 549
6663
Note:
AFD input amps are shown in the RLA field of the unit nameplate.
Summary of Contents for Optimus RTHD
Page 27: ...Installation Mechanical RTHD SVX01K EN 27...
Page 28: ...Installation Mechanical 28 RTHD SVX01K EN...
Page 29: ...Installation Mechanical RTHD SVX01K EN 29...
Page 54: ...Controls 54 RTHD SVX01K EN Figure 23 Tracer TU...
Page 88: ...Log and Check Sheets 88 RTHD SVX01K EN Page Left Intentionally Blank...
Page 95: ...Notes RTAF SVX001K EN 95...