Diagnostics
RTHD-SVX01K-EN
77
Evap Water Flow
(Entering Water
Temp)
Chiller
Warning
NonLatch
Any Ckt(s)
Energized [No
Ckt(s) Energized]
The entering evaporator water temp fell below the leaving
evaporator water temp. by more than 2°F for 100 °F-sec.
For falling film evaporators this diagnostic cannot reliably
indicate loss of flow, but can warn of improper flow
direction through the evaporator, mis-bound temperature
sensors, or other system problems
Remote
Evaporator Diff
Water Pressure
Xdcr
Chiller
Warning
Latching
All
Defective Sensor or LLID
a. Display invalid value
b. Flow calculation shall be disabled.
c. See Water Flow and Tons Sensing specification for
additional information.
Remote
Evaporator
Entering Water
Temp Sensor
Chiller
Warning
and Special
Action
Latch
Bad Sensor or LLID Normal operation unless CHW Reset is
enabled. If CHW Reset is enabled and either Return or
Constant Return Chilled Water Reset is selected, its effect
will be removed but slew rates on the change will be limited
per the Chilled Water Reset spec.
Remote
Evaporator
Leaving Water
Temp Sensor
Chiller
Normal
Latch
All
Bad Sensor or LLID
Remote
Evaporator
Liquid Level
Sensor
Chiller
Normal
Latch
All
Bad Sensor or LLID
Remote
Evaporator Rfgt
Pressure
Transducer
Chiller
Normal
Latch
All
Bad Sensor or LLID
Remote
Evaporator
Water Flow Lost
Chiller
Immediate NonLatch
Evap pump
commanded “on”
except for [All Stop
modes]
The Evaporator water flow proof input was open for more
than 6-10 contiguous seconds after flow had been proven.
The pump command status will not be effected. Even
though the pump may be commanded to run in the STOP
modes (pump off delay time), this diagnostic shall not be
called out in the STOP modes. This diagnostic will auto-
clear on proof of flow (6-10 seconds of continuous flow),
or if chiller is returned to Stop mode.
Remote
Evaporator
Water Flow
Overdue
Chiller
Normal
NonLatch
Estab. Evap. Water
Flow on going from
STOP to AUTO.
Evaporator water flow was not proven within 20 minutes of
the Evaporator water pump relay being energized. The
Evap pump command status will not be effected. This
diagnostic will auto-clear on proof of flow (6-10 seconds of
continuous flow), or if chiller is returned to Stop mode.
Remote
Excessive
Condenser
Pressure
Chiller
Immediate Latch
All
The condenser pressure transducer of this chiller has
detected a pressure in excess of the safe high side pressure
as limited by the particular compressor type or the
evaporator distributor present on this particular chiller.
Remote
External Base
Loading Setpoint
Chiller
Info and
Special
Action
NonLatch
All
a. Not ""Enabled"": no diagnostics. b. ""Enabled "": Out-
Of-Range Low or Hi or bad LLID, set diagnostic, default
BLS to next level of priority (e.g. Front Panel SetPoint. This
Info diagnostic will automatically reset if the input returns
to the normal range.
Remote
External Chilled/
Hot Water
Setpoint
Chiller
Warning
NonLatch
All
a. Function Not "Enabled": no diagnostics. b. "Enabled":
Out-Of-Range Low or Hi or bad LLID, set diagnostic,
default CWS to next level of priority (e.g. Front Panel
SetPoint). This Info diagnostic will automatically reset if
the input returns to the normal range.
Remote
External
Demand Limit
Setpoint
Chiller
Warning
NonLatch
All
a. Not "Enabled": no diagnostics. b. "Enabled": Out-Of-
Range Low or Hi or bad LLID, set diagnostic, default DLS
to next level of priority (e.g. Front Panel SetPoint. This Info
diagnostic will automatically reset if the input returns to
the normal range.
Remote
External Heat
Recovery Tank
Water
Temperature
Setpoint Input
Heat
Recovery
Warning
NonLatch
All
Bad Sensor or LLID.
Remote
Table 26. Main processor diagnostics (continued)
Diagnostic
Name and
Source
Affects
Target Severity
Persistence
Active Modes
[Inactive
Modes]
Criteria
Reset
Level
Summary of Contents for Optimus RTHD
Page 27: ...Installation Mechanical RTHD SVX01K EN 27...
Page 28: ...Installation Mechanical 28 RTHD SVX01K EN...
Page 29: ...Installation Mechanical RTHD SVX01K EN 29...
Page 54: ...Controls 54 RTHD SVX01K EN Figure 23 Tracer TU...
Page 88: ...Log and Check Sheets 88 RTHD SVX01K EN Page Left Intentionally Blank...
Page 95: ...Notes RTAF SVX001K EN 95...