Drive and Cabinet
Enclosure Rating
The Trane® cabinet has a NEMA 1 enclosure rating:
NEMA 1: Vented. Intended for general-purpose indoor
applications.
Environmental Conditions
Important:
Location of the AFDE is important if proper
performance and normal operating life is to
be expected. Therefore, unless designed for
special environments, the controller should
be installed in an area where the following
conditions exist
•
Verify that NEMA 1 enclosure drives can be kept clean
and dry.
•
The area chosen should allow the space required for
proper air flow. Adequate clearance for air circulation
around the enclosure is a 6 inch (15.25 cm) minimum
clearance required wherever vents are located in the
cabinet.
•
Be sure that the NEMA 1 enclosure is installed away
from oil, coolants, or other airborne contaminants.
•
Do not install the drive above 3300 feet (1000 meters)
without derating output power. For every 300 feet
(91.4 meters) above 3300 feet (1000 meters), derate
the output current 1%.
•
Line frequency is 50 or 60 Hz.
•
Line Voltage is 380–480 volts; variation are within
+10%.
•
Non-corrosive location.
•
Verify that the drive location will meet the
environmental conditions specified in Table 1.
Identifying Trane AFDE Cabinet
Components
Trane AFDE cabinets have the following main
components. For convenience, the drive is discussed in
two sections, a rectifier (input) and inverter (output)
sections. See
Figure 1, p. 15
and
Figure 3, p. 18
for Frame
3, and
Figure 4, p. 19
,
Figure 5, p. 21
and
Figure 7, p. 24
for
Frame 4.
Drive Cabinet Component
Locations
Frame 3 Units
179910-903 and 179910-905
The main drive components for a Frame 3 unit are listed
below. Each numbered item corresponds to a number in
Figure 1
.
1. Circuit Breaker, 600V
2. Circuit Breaker Operating Mechanism
3. Inductor
4. AC Contactor
5. Power Module Assembly (refer to
Figure 3, p. 18
and
Figure 4, p. 19
for details)
6. Input Filter Capacitor Assembly
7. Input Filter Capacitor Guard Panel
8. Fans, 115Vac, Inductor (2)
9. Transformer, 3kVA
10. Fan, 115Vac, Contactor
11. Resistors, 100k Ohms, 50W
12. Precharge Resistors
13. Relay, Oil Pump and Control Power Terminals
14. Fuse, Class RK-5, 600V, 15A (2)
15. Fuse, Class CC, 600V, 25A (1)
16. Fuse, Class CC, 600V, 5A (1)
17. Fuse, Class T, 500V, 150A (3)
18. Fuse, Class CC, 600V, 20A (3)
19. Fuse, Class CC, 600V, 1A (3)
20. Ground Lug, 2–600 MCM (for AWG/MCM equivalents
in mm2, refer to
)
21. Nameplate, Power Module
22. Door Inter-lock
Table 1.
Environmental conditions
Condition
Specification
Operating Temperature
(inside NEMA 1 enclosure)
32° to 131°F (0°C to + 55°C)
Ambient Temperature
(outside NEMA 1 enclosure)
32°F to 104°F (0°C to + 40°C)
Storage Temperature (Ambient) -40°F to 149°F (-40°C to 65°C)
Humidity
5% to 95% (non-condensing)