Input Power and Control Wiring
34
AFDE-SVU02F-EN
Note:
Graphic labels (shown above) are used for CE
application only.
Important:
•
Before servicing, disconnect all power sources and
allow at least 10 minutes for capacitors to discharge.
•
All electrical enclosures-unit or remote-are IP2X.
An input disconnect circuit breaker is factory-installed in
the cabinet. Verify that the available fault current is less
than the interrupting rating on the circuit breaker
nameplate, which is 65,000 amps at 480 Vac.
WARNING
Proper Field Wiring and Grounding
Required!
Failure to follow code could result in death or serious
injury. All field wiring MUST be performed by qualified
personnel. Improperly installed and grounded field
wiring poses FIRE and ELECTROCUTION hazards. To
avoid these hazards, you MUST follow requirements for
field wiring installation and grounding as described in
NEC and your local/state electrical codes.
NOTICE
Equipment Damage!
Failure to follow instructions below could result in
damage to equipment. Do not route signal and control
wiring with power wiring in the same conduit. This can
interfere with drive operation.
X39003893001A