Input Power and Control Wiring
AFDE-SVU02F-EN
33
Note:
Graphic labels (shown above) are used for CE
application only.
Important:
•
Before servicing, disconnect all power sources and
allow at least 10 minutes for capacitors to discharge.
•
All electrical enclosures-unit or remote-are IP2X.
Grounding the Cabinet
Note:
Follow Applicable Codes! The user is responsible
for conforming to all applicable, local, national, and
international codes. Failure to observe this
precaution could result in damage to, or
destruction of, the equipment.
Use the following steps to ground the cabinet:
1. Open the left-hand enclosure door of the drive. The
grounding stud is located just above and to the right of
the breaker.
2. Run a suitable earth ground (completed by field) to the
cabinet’s ground connection point. The grounding lug
is capable of accepting up to 2–600 MCM wire. For
AWG/MCM equivalents in mm2, refer to
Tighten the ground connections to 375 in·lb
(42.4 N·m).
WARNING
Hazardous Voltage/Improper Grounding!
Hazardous voltage due to improperly grounded
electrical components could result in death or serious
injury. The motor controller has a chassis ground that
must be connected to an earth ground.
X39003893001A
Table 4.
Standard wiring requirements AFD control wiring (between the chiller and the starter)
AFD Starter to Control Panel
Control Wiring
Starter Panel
Terminations
Control Panel Terminations
Comment
CVHE, CVHF,
CVHG
CVHH
AFD 120Vac Power Supply (hot)
2X1-1
1X1-1
1X1-1
AFD 120Vac Power Supply (neutral)
2X1-15
1X1-12
Ground
2X1-11
1X1-G
1X1-G
Panel ground.
Ref/Oil Pump Interlock (2K11)
2X1-7, 2X1-8
LLID 1A7
J2-4, J2-2
LLID 1K17
J2-3, J2-1
Normally open.
Condenser High Pressure Cutout (3S1)
2X1-3, 2X1-4
(shield to 2X1-5)
N/A
N/A
Normally closed. Operates the gate kill
input on 2A2-TB33.
Recomm Bus +24V
2A32-1
WB2 to 1A1, J4-1
WB2 to 1T2, J4-1
4-wire bus WB2 connects to power
supply module, terminals J4-1, 2, 3,
and 4
Recomm Bus Ground
2A32-2
WB2 to 1A1, J4-2
WB2 to 1T2, J4-2
Recomm Bus Com +
2A32-3
WB2 to 1A1, J4-3
WB2 to 1T2, J4-3
Recomm Bus -
2A32-4
WB2 to 1A1, J4-4
WB2 to 1T2, J4-4