CTV-SVX009D-GB
9
11
UNT-PRC002-GB
Sound power levels
Discharge
Measurement conditions:
Measurements taken in a room adjacent to the room containing the FWD, at the outlet of the rectangular duct (1.5 m
long) fixed to its discharge opening.
Fan
Power level in dB(A), per Hz frequency band
Overall power
Unit
speed
125
250
500
1000
2000
4000
8000
dB(A)
1
55
50
42
37
37
31
30
46
FWD 08
2
57
54
47
40
30
38
40
50
3
58
57
50
42
32
40
43
53
1
57
51
45
42
34
33
28
48
FWD 10
2
58
54
48
45
38
39
35
51
3
60
58
50
48
40
42
39
54
1
57
51
45
42
34
33
28
48
FWD 12
2
58
54
48
45
38
39
35
51
3
60
58
50
48
40
42
39
54
1
56
62
50
48
39
38
36
56
FWD 14
2
61
66
55
53
47
46
45
60
3
63
69
58
56
50
50
49
63
1
57
63
51
49
40
39
37
57
FWD 20
2
61
66
55
53
47
46
45
60
3
63
69
58
56
50
50
49
63
Intake
Measurement conditions:
Measurements taken at the horizontal air intake.
Fan
Power level in dB(A), per Hz frequency band
Overall power
Unit
speed
125
250
500
1000
2000
4000
8000
dB(A)
1
56
55
55
53
46
45
42
57
FWD 08
2
63
62
60
60
53
53
53
64
3
66
65
63
62
56
55
57
67
1
62
58
55
58
51
48
44
61
FWD 10
2
66
63
60
62
56
55
52
66
3
70
67
63
65
59
59
57
69
1
62
58
55
58
51
48
44
61
FWD 12
2
66
63
60
62
56
55
52
66
3
70
67
63
65
59
59
57
69
1
66
65
65
65
57
50
46
68
FWD 14
2
73
72
69
71
64
59
57
74
3
78
76
73
75
69
64
63
78
1
68
72
64
64
56
52
50
69
FWD 20
2
76
76
68
71
65
61
61
75
3
78
79
71
74
69
66
66
78
GVAF XP
190
205
245
310
350
Extra Low Noise fan option
Fan / motor Type
Airflow per Fan
(m3/h)
20000
20000
20000
20000
20000
Max Power input per Motor
(kW)
1.1
1.1
1.1
1.1
1.1
Max Amps per Motor
(A)
1.8
1.8
1.8
1.8
1.8
Motor RPM
(rpm)
860
860
860
860
860
System data (8)
Nb of refrigerant circuit
#
2
2
2
2
2
Minimum cooling load % (4)(7)
%
28
26
23
25
22
R134a refrigerant charge Circuit1 / Circuit 2 (8)
(kg)
140/75
140/75
140/75
140/140
140/140
(1) Indicative performance at Evaporator water temperature: 12°C / 7°C - Condenser air temperature 35°C - for detailed performances consult
Order Write Up.
(2) Under 400V/3/50Hz.
(3) Rated Condition without Pump Package.
(4) Percent minimum load may be adjusted around 15%-20% according to operating conditions by local sales office.
(5) Electrical & system data are indicative and subject to change without notice. Please refer to unit nameplate data.
(6) Not applicable for Glycol application - see tables with Minimum Flow with Glycol.
(7) Max speed - range is 60% to 100% of max speed.
(8) Refrigerant charge may vary according to option. For real value refer to unit nameplate.
(9) Data containing information on two circuits shown as follows: ckt1/ckt2.
General Data
Table 2 – General Data GVAF 190-350 : Extra Efficiency Low Noise and Extra Low Noise -R134a/R513A (continued)