Dimensions
and Weights
PKG-PRC002-EN
92
Service/Code Clearance Requirements
Side
Distance
Purpose
Front
42 in. (1066 mm) (20-38 Ton)
NEC code requirement
48 in. (1219 mm) (42-80 Ton)
Fan service/removal
Left
36 in. (914 mm)
Filter, refrigeration and waterside component service
Right
9 in. (229 mm)
Non VFD w/ open return
18 in. (457 mm)
Non VFD w/ ducted return
24 in. (610 mm)
w/ VFD 7.5 to 20 HP
36 in. (914 mm)
w/ VFD 25 to 50 HP
Inlet
18 in. (457 mm)
Provides uniform airflow
Service
Clearances
Self-Contained Models
SCWF/SIWF/SCRF/SIRF
Air Inlet
18” (457.2mm)
Minimum
See Table
42” (1066.8mm) (20-38 Ton)
Minimum
48” (1219mm) (42-80 Ton)
Control
Panel
36” (914.4mm)
Minimum
Top View
SCWF/SCRF/SIWF/SIRF
Summary of Contents for CCRC20