Performance
Water-Cooled
Data
PKG-PRC002-EN
39
29 Ton
Note:
1. Fan curves include refrigerant coil and internal cabinet
static losses. To determine static pressure to be used
with these curves, add filter, economizer, flexible
horizontal discharge and heat pressure drops to
external duct static pressure.
Chart PD-34. SCWF/SIWF 29 Fan Performance with Inlet Guide Vanes
Table PD-13. SCWF/SIWF 29 Gross Cooling Capacity - 11,600 cfm, 87 gpm
Entering Water Temp
Entering Air
75 F
85 F
95 F
EDB
EWB
Total
Sensible
Total
Sensible
Total
Sensible
F
F
MBh
MBh
LWT
MBh
MBh
LWT
MBh
MBh
LWT
62
335
266
84.2
323
259
94.1
309
254
104.0
75
67
365
211
84.9
352
206
94.8
337
201
104.7
72
397
157
85.6
383
152
95.5
366
146
105.4
62
336
315
84.2
325
309
94.1
311
301
104.0
80
67
365
262
84.9
352
256
94.8
337
251
104.6
72
396
208
85.6
381
202
95.5
366
196
105.4
62
347
347
84.4
337
337
94.4
325
325
104.3
85
67
365
312
84.9
351
306
94.8
337
300
104.7
72
396
258
85.6
381
253
95.5
366
246
105.3
Chart PD-33. SCWF/SIWF 29 Fan Performance for CV or with VFD
Summary of Contents for CCRC20
Page 81: ...Dimensions and Weights PKG PRC002 EN 81 Self Contained 20 38 Tons 20 38Ton Self Contained...
Page 82: ...Dimensions and Weights PKG PRC002 EN 82 40 80Ton Self Contained Self Contained 40 80 Ton 82...
Page 88: ...Dimensions and Weights PKG PRC002 EN 88 Airside Economizer Airside Economizer...