Performance
Water-Cooled
Data
PKG-PRC002-EN
45
38 Ton
Note:
1. Fan curves include refrigerant coil and internal cabinet
static losses. To determine static pressure to be used
with these curves, add filter, economizer, flexible
horizontal discharge and heat pressure drops to
external duct static pressure.
Table PD-22. SCWF/SIWF 38 Gross Cooling Capacity - 15,200 cfm, 114 gpm
Entering Water Temp
Entering Air
75 F
85 F
95 F
EDB
EWB
Total
Sensible
Total
Sensible
Total
Sensible
F
F
MBh
MBh
LWT
MBh
MBh
LWT
MBh
MBh
LWT
62
434
373
83.9
416
365
93.8
398
357
103.7
75
67
471
290
84.6
452
283
94.5
432
275
104.3
72
511
206
85.3
490
199
95.2
469
192
105.0
62
441
441
84.1
426
426
94.0
410
410
103.9
80
67
470
369
84.6
452
361
94.5
432
353
104.3
72
510
285
85.3
490
277
95.2
468
270
105.0
62
465
465
84.5
450
450
94.4
433
433
104.4
85
67
473
444
84.7
455
435
94.5
436
425
104.4
72
510
363
85.3
489
355
95.2
468
348
105.0
Chart PD-39. SCWF/SIWF 38 Fan Performance for CV or with VFD
Chart PD-40. SCWF/SIWF 38 Fan Performance with Inlet Guide Vanes