Performance
Water-Cooled
Data
PKG-PRC002-EN
59
80 Ton
Note:
1. Fan curves include refrigerant coil and internal cabinet
static losses. To determine static pressure to be used
with these curves, add filter, economizer, flexible
horizontal discharge and heat pressure drops to
external duct static pressure.
Table PD-43. SCWF/SIWF 80 Gross Cooling Capacity - 29,800 cfm, 240 gpm
Entering Water Temp
Entering Air
75 F
85 F
95 F
EDB
EWB
Total
Sensible
Total
Sensible
Total
Sensible
F
F
MBh
MBh
LWT
MBh
MBh
LWT
MBh
MBh
LWT
62
891
761
83.7
856
746
93.6
819
729
103.4
75
67
966
590
84.3
928
575
94.2
887
559
104.0
72
1049
419
85.0
1007
405
94.8
963
389
104.7
62
910
896
83.8
880
867
93.8
847
834
103.7
80
67
967
752
84.3
929
737
94.2
888
721
104.0
72
1048
579
85.0
1006
565
94.8
963
550
104.7
62
961
947
84.3
930
916
94.2
896
883
104.1
85
67
975
908
84.4
938
890
94.3
899
871
104.1
72
1047
740
85.0
1006
725
94.8
963
710
104.7
Chart PD-53. SCWF/SIWF 80 Fan Performance for CV or with VFD
Chart PD-54. SCWF/SIWF 80 Fan Performance with Inlet Guide Vanes