Performance
Water-Cooled
Data
PKG-PRC002-EN
37
25 Ton
Note:
1. Fan curves include refrigerant coil and internal cabinet
static losses. To determine static pressure to be used
with these curves, add filter, economizer, flexible
horizontal discharge and heat pressure drops to external
duct static pressure.
Table PD-10. SCWF/SIWF 25 Gross Cooling Capacity - 10,000 cfm, 75 gpm
Entering Water Temp
Entering Air
75 F
85 F
95 F
EDB
EWB
Total
Sensible
Total
Sensible
Total
Sensible
F
F
MBh
MBh
LWT
MBh
MBh
LWT
MBh
MBh
LWT
62
281
234
83.9
270
229
93.8
259
224
103.6
75
67
306
184
84.5
294
179
94.4
281
174
104.3
72
332
133
85.3
319
129
95.1
305
124
105.0
62
284
278
83.9
274
272
93.8
263
263
103.8
80
67
306
231
84.5
294
227
94.4
281
221
104.3
72
332
180
85.3
319
176
95.1
305
171
104.9
62
298
298
84.3
288
288
94.3
278
278
104.2
85
67
306
278
84.6
295
272
94.4
283
267
104.3
72
332
228
85.2
319
223
95.1
305
218
104.9
Chart PD-31. SCWF/SIWF 25 Fan Performance for CV or with VFD
Chart PD-32. SCWF/SIWF 25 Fan Performance with Inlet Guide Vanes