Performance
Air-Cooled
Data
PKG-PRC002-EN
61
25 Ton
Note:
1. Fan curves include refrigerant coil and internal cabinet
static losses. To determine static pressure to be used
with these curves, add filter, economizer, flexible
horizontal and heat discharge pressure drops to external
duct static pressure.
Table PD-45. SCRF/SIRF 25 Gross Cooling Capacity - 11,600 cfm
Entering Ambient Air Temperature
75 F
85 F
95 F
105 F
115 F
EDB EWB
Tot
Sen
Tot
Sen
Tot
Sen
Tot
Sen
Tot
Sen
F
F
MBh
MBh
MBh
MBh
MBh
MBh
MBh
MBh
MBh
MBh
70
62
336.8
214.8
325.2
209.5
312.8
204.0
299.6
198.1
285.7
192.0
67
367.8
161.8
355.1
156.6
341.7
151.1
327.5
145.5
312.4
139.5
62
336.5
265.4
324.9
260.1
312.5
254.5
299.4
248.7
285.5
242.5
75
67
367.4
212.3
354.8
207.1
341.4
201.6
327.2
195.9
312.1
189.9
72
400.2
158.7
386.5
153.6
372.0
148.3
356.6
142.8
340.3
137.0
62
337.8
315.3
326.7
309.5
315.1
303.1
303.0
296.0
290.7
287.2
80
67
367.1
262.6
354.5
257.3
341.1
251.8
326.9
246.1
311.9
240.0
72
399.9
208.8
386.2
203.7
371.7
198.4
356.3
192.8
340.0
187.0
62
349.9
350.0
340.3
340.4
329.9
329.9
318.7
318.7
306.7
306.8
85
67
366.9
312.6
354.5
307.3
341.3
301.6
327.4
295.6
312.9
289.1
72
399.6
258.8
385.9
253.6
371.3
248.2
356.0
242.6
339.8
236.7
Chart PD-58. SCRF/SIRF 25 Fan Performance with Inlet Guide Vanes
Chart PD-57. SCRF/SIRF 25 Fan Performance for CV or with VFD
Summary of Contents for CCRC20
Page 81: ...Dimensions and Weights PKG PRC002 EN 81 Self Contained 20 38 Tons 20 38Ton Self Contained...
Page 82: ...Dimensions and Weights PKG PRC002 EN 82 40 80Ton Self Contained Self Contained 40 80 Ton 82...
Page 88: ...Dimensions and Weights PKG PRC002 EN 88 Airside Economizer Airside Economizer...