Performance
Water-Cooled
Data
PKG-PRC002-EN
55
65 Ton
Note:
1. Fan curves include refrigerant coil and internal cabinet
static losses. To determine static pressure to be used
with these curves, add filter, economizer, flexible
horizontal discharge and heat pressure drops to
external duct static pressure.
Table PD-37. SCWF/SIWF 65 Gross Cooling Capacity - 26,000 cfm, 196 gpm
Entering Water Temp
Entering Air
75 F
85 F
95 F
EDB
EWB
Total
Sensible
Total
Sensible
Total
Sensible
F
F
MBh
MBh
LWT
MBh
MBh
LWT
MBh
MBh
LWT
62
744
609
84.1
715
597
93.9
686
583
103.8
75
67
809
480
84.8
779
468
94.6
746
455
104.5
72
879
351
85.5
845
338
95.4
810
326
105.2
62
749
726
84.1
722
711
94.0
694
692
104.0
80
67
809
601
84.8
778
589
94.6
746
576
104.5
72
878
471
85.5
844
459
95.4
810
447
105.2
62
780
780
84.5
756
756
94.4
730
730
104.4
85
67
809
721
84.8
779
708
94.6
747
695
104.5
72
877
592
85.5
844
579
95.4
808
567
105.2
Chart PD-49. SCWF/SIWF 65 Fan Performance for CV or with VFD
Chart PD-50. SCWF/SIWF 65 Fan Performance with Inlet Guide Vanes