Mechanical
Specifications

PKG-PRC002-EN

95

Signature Series Self-
Contained Units

Cabinet

The unit framework shall be formed
structural steel members of 14-gauge
galvanized steel. Exterior panels shall be
fabricated from 18-gauge galvanized
steel. The fan and compressor sections
shall be insulated with ¾-inch (19 mm) of
1.75 lb./cu. ft. (28 kg./cu. ft.) density
fiberglass insulation.

The unit shall be provided with removable
panels to allow service access to
compressors, condensers, fan motor, fan
bearings, coils, and valves. Removable
panels shall be secured with quick-acting
fasteners. The refrigerant sight glasses
shall be accessible during operation. The
control panel door shall have lift-off
hinges.

Compressors

Units shall have multiple compressors
with independent circuits for water-cooled
units and manifolded circuits for air-
cooled units. Compressors shall be
manufactured by the unit manufacturer.
Scroll compressors shall be heavy duty
suction cooled type with suction screen,
centrifugal oil pump with dirt separator, oil
charging valve, and oil sight glass.
Protective devices for low pressure, high
pressure, and motor temperature shall be
provided. The compressors shall be
mounted on isolators for vibration
isolation.

Condenser (SCWF/SIWF only)

One condenser shall be provided for each
compressor. The condensers shall be
shell-and-tube design with removable
heads and mechanically cleanable tubes.
Tubes shall be ¾-inch (19mm) OD and
constructed of copper. Condenser
waterside working pressure shall be 400
psig. All condenser water piping including,
cleanouts, shall be factory installed to
provide single connections for water inlet
and outlet.

Evaporator

The evaporator coil shall be seamless
copper tubes expanded into aluminum
fins. Tubes shall be ½-inch (13mm) OD
with internally enhanced surfaces. Coil
shall have staggered tube arrangement

with intertwined circuiting and no more
than 12 fins per inch.

The drain pan shall be positively sloped in
all directions to ensure proper condensate
removal. The drain pan shall be fabricated
of galvanized steel and insulated with ¾-
inch (19 mm) of 1-lb. (0.5 kg) density
fiberglass. Drain piping, including a trap
with cleanout, shall be provided with a
single-point connection to the unit’s
exterior.

Refrigerant Circuit (SCWF only)

Refrigerant circuits shall be independent
and completely piped including sight
glasses, distributors, thermal expansion
valves with adjustable superheat and
external equalizer, and high pressure
relief valves with ½-inch (13 mm) flare
connection. Filter driers ship loose for field
installation. Unit shall be provided with
adequate means of frost control. The
circuits shall be factory dehydrated,
charged with oil and refrigerant 22.
Compressors shall be mounted on
rubber-in-shear isolators for vibration
isolation.

Refrigerant Circuit (SCRF/SIRF only)

Two refrigerant circuits shall be piped to
the unit’s exterior. The refrigerant piping
includes filter driers (for field installation),
sight glasses, distributors, thermal
expansion valves with adjustable
superheat and external equalizer. Unit
shall be provided with adequate means of
frost control. The circuits shall be factory
tested, dehydrated and then charged with
dry nitrogen. Compressors shall be
mounted on rubber-in-shear isolators for
vibration isolation.

Supply Fan

The supply fan shall be a single forward
curved medium pressure fan secured to a
solid steel shaft with grease lubricated
bearings designed for 200,000 hours.
Both fan bearings shall have greaselines
extended to a common location. The drive
components shall include fixed pitch
sheaves and multiple V-belt sized for
130% nominal motor horsepower. The
supply fan motor shall have a service
factor of 1.15. The supply fan motor shall
be either:

Standard efficiency open drip-proof

Premium efficiency open drip-proof

 Totally enclosed fan cooled standard

efficiency.

Supply fan motor shall have a standard T-
frame. All drive components shall be
accessible without using scaffolds or
ladders.

The entire fan assembly, including drive
components, shall be mounted on a
common base. The fan base shall be
isolated inside the unit. The entire
assembly shall be statically and
dynamically balanced at the factory.

Filters

Two-inch (51 mm) throwaway fiberglass
filters shall be provided for installation
during construction.

Unit Controls - DDC

Microprocessor controls shall be provided
to control all unit functions. The control
system shall be suitable to control CV or
VAV applications. The controls shall be
factory-installed and mounted in the main
control panel. All factory-installed controls
shall be fully commissioned (run tested) at
the factory. The unit shall have a human
interface panel with 16-key keypad, a
two line, 40 character clear language
(English, French, or Spanish) display as
standard to provide the operator with full
adjustment and display of control data
functions. The unit controls shall be used
as a stand-alone controller or as part of a
building management system involving
multiple units.

The unit shall be equipped with a
complete microprocessor control system.
This system shall consist of temperature
and pressure (thermistor and static
pressure transducer) sensors, printed
circuit boards (modules) and a unit
mounted human interface panel. Modules
(boards) shall be individually replaceable
for service ease. All microprocessors,
boards, and sensors shall be factory
mounted, wired, and tested.

The microprocessor boards shall be
stand-alone DDC controls not dependent
on communications with an on-site PC or
building management network. The
microprocessors shall be equipped with
on-board diagnostics, indicating that all
hardware, software, and interconnecting
wiring are in proper operating condition.
The modules (boards) shall be protected
to prevent RFI and voltage transients
from affecting the board’s circuits. All field

Self-Contained

Summary of Contents for CCRC20

Page 1: ...December 2001 PKG PRC002 EN CommercialSelf Contained IntelliPak Signature Series 20 80 T on Water Cooled Air Conditioners 20 60 T on Air Cooled Air Conditioners Remote Air Cooled Condensers...

Page 2: ...optionshown Sightglasseswith portsforviewing whileunitisrunning Hingedandremovablecontrol panel door for easy access Unitmountedmicroprocessor controlwitheasy to readhuman interfacepanel Energysavings...

Page 3: ...lection Procedure 12 Model Number Description 14 General Data 17 Performance Data 22 Airside Pressure Drops 22 Waterside Pressure Drops 29 Water Cooled Units 31 Air Cooled Units 60 Heating Coils 68 Co...

Page 4: ...r system since only units on floors requiring cooling need to operate Significant annual energy consumption reduction due to partial occupancy after hours when compared to a central chilled water syst...

Page 5: ...module Generic BAS interface Comparative enthalpy control Ventilation override from up to five external inputs Remote human interface controls up to four units Fully integrated factory installed commi...

Page 6: ...your facility all from your personal computer The IntelliPak self contained unit as part ofTrane ICS provides powerful maintenance monitoring control and reporting capabilities Tracer places the self...

Page 7: ...cies The most outstanding feature of the scroll compressor 3 D compliance is that slugging will not cause failure In a reciprocating compressor however liquid or dirt can cause serious damage Low Torq...

Page 8: ...exterior of the equipment room Use a minimum ductwork length of 15 feet to the equipment room exterior Line the duct with two inch three pound density insulation Use multiple small return ducts for be...

Page 9: ...ransmission to or from the building plumbing The Signature Series self contained unit is internally isolated and does not require additional isolation However ensure proper system vibration isolation...

Page 10: ...ondensing water applications between 35 F 1 7 C and 54 F 12 2 C require a condensing pressure control valve Any unit with variable flow waterside valves can modulate water flow to maintain a user defi...

Page 11: ...it Nuisance high head pressure tripouts may also occur The coil inlet must also be unobstructed A unit installed closer than the minimum recommended distance to a wall or other vertical riser will exp...

Page 12: ...heat by using the following equation Fan motor heat MBh 2 8 x fan motor brake horsepower 7 Determine net total capacity and net sensible capacity by subtracting fan motor heat from gross total capacit...

Page 13: ...age 42 Use entering air of 80 67 and entering water temperature of 55 deg F at 105 gpm The table provides a gross total capacity of 282 1 MBh and gross sensible capacity of 277 2 MBh and 60 4 deg F le...

Page 14: ...d Plenum w Field Cut Holes F Low Plenum w Field Cut Holes H Std Plenum Double wall w Field Cut Holes J Low Plenum Double wall w Field Cut Holes K 45 Plenum w Factory Cut Holes Ship Separate L Std Plen...

Page 15: ...E GBAS and TCI F VOM and TCI G GBAS and VOM H GBAS and RHI J VOM and RHI K TCI and RHI L GBAS VOM and TCI M GBAS VOM and RHI N GBAS TCI and RHI P VOM TCI and RHI R GBAS VOM TCI and RHI 0 None Digit 3...

Page 16: ...3 ph 5 575Volt 60 Hz 3 ph 6 200Volt 60 Hz 3 ph Digit 9 Control Option 0 No LowAmbient Damper I Pak A No Low Ambient Damper T Stat B Low Ambient I Pak C Low Ambient T Stat Digit 10 11 Design Sequence...

Page 17: ...4 24 24 24 25 24 25 Circuit C 24 25 Refrigerant Charge kg R 22 Circuit A 10 9 10 9 10 9 12 7 13 6 10 9 11 3 Circuit B 10 9 10 9 10 9 10 9 11 3 10 9 11 3 Circuit C 10 9 11 3 Capacity Steps 100 53 0 100...

Page 18: ...2 Circuit D 24 25 32 Refrigerant Charge kg R 22 Circuit A 12 7 13 6 12 7 13 6 12 7 13 6 14 5 Circuit B 10 9 11 3 12 7 13 6 12 7 13 6 14 5 Circuit C 10 9 11 3 12 7 13 6 12 7 13 6 14 5 Circuit D 10 9 11...

Page 19: ...0 100 70 41 30 0 100 65 30 0 100 73 46 20 0 Filter Data Quantity 8 8 8 8 8 4 4 4 Size inches 20x18x2 20x18x2 20x18x2 20x18x2 20x18x2 16x20x2 16x20x2 16x20x2 Size mm 508x457x51 508x457x51 508x457x51 5...

Page 20: ...115 0 115 Low Ambient Option C 17 8 46 1 17 8 46 1 17 8 46 1 17 8 46 1 17 8 46 1 17 8 46 1 Notes 1 Gross Heat Rejection is at a 20 F 6 7 C ITD InitialTemperature Difference between condensing temperat...

Page 21: ...2 2 762x2057 4 FPF 80 80 80 80 Filter Data Quantity 4 4 4 4 Size inches 20x18x2 16x20x2 20x18x2 16x20x2 Size mm 508x457x51 406x508x51 508x457x51 406x508x51 Quantity 8 8 8 8 Size inches 20x20x2 16x25x2...

Page 22: ...on construction filters indicates cfm where face velocity exceeds manufacturer s recommended maximum of 300 fpm After startup construction filters must be replaced with medium velocity or high velocit...

Page 23: ...sure Drop SCWF SIWF 72 Notes 1 Dotted line on construction filters indicates cfm where face velocity exceeds manufacturer s recommended maximum of 300 fpm After startup construction filters must be re...

Page 24: ...ance Airside Pressure Data Drops PKG PRC002 EN 24 Chart PD 9 Airside Pressure Drop Steam Coil 20 to 80 Ton Units For NS Coils Heating Coils Chart PD 10 Airside Pressure Drop Hot Water Coil 20 to 80 To...

Page 25: ...ssure for proper fan horsepower determination Discharge Plenum Chart PD 11 Airside Pressure Drop Standard Height Discharge Plenum 42 to 80Ton Unit Chart PD 12 Airside Pressure Drop Low Height Discharg...

Page 26: ...essure Data Drops PKG PRC002 EN 26 Chart PD 14 Airside Pressure Drop Extended Height Discharge Plenum 20 to 38 Ton Unit Chart PD 15 Airside Pressure Drop Extended Height Discharge Plenum 42 to 80 Ton...

Page 27: ...PKG PRC002 EN 27 Airside Economizer with Standard Damper Chart PD 16 Airside Pressure Drop Airside Economizer with Standard Damper 20 to 38 Ton Unit Chart PD 17 Airside Pressure Drop Airside Economize...

Page 28: ...Performance Airside Pressure Data Drops PKG PRC002 EN 28 Airside Economizer with T raq Damper Chart PD 18 Airside Pressure Drop Airside Economizer withTraq Damper Air Flow Rate CFM...

Page 29: ...hart PD 20 Waterside Pressure Drop SCWF SIWF 29 32 Chart PD 21 Waterside Pressure Drop SCWF SIWF 35 38 Chart PD 22 Waterside Pressure Drop SCWF SIWF 42 46 Note Each curve provides total water pressure...

Page 30: ...8 Chart PD 24 Waterside Pressure Drop SCWF SIWF 65 Chart PD 25 Waterside Pressure Drop SCWF SIWF 72 Chart PD 26 Waterside Pressure Drop SCWF SIWF 80 Note Each curve provides total water pressure drop...

Page 31: ...ionTable Cfm Compared Cooling Sensible To Rated Capacity Capacity Quanitity Multiplier Multiplier 20 0 970 0 910 10 0 985 0 955 DX Cooling Std 1 000 1 000 3 1 005 1 014 6 1 009 1 027 20 0 970 0 910 10...

Page 32: ...8 208 8 61 0 50 340 7 219 3 58 6 230 6 180 5 64 2 72 60 364 4 228 2 57 1 244 2 185 1 63 1 70 382 6 235 1 55 9 255 1 188 8 62 3 20 Ton Table PD 3 SCWF SIWF 20 Economizer Low Capacity 8 000 cfm Entering...

Page 33: ...226 209 104 6 80 67 266 183 85 5 256 179 95 4 245 174 105 3 72 289 147 86 3 278 143 96 1 267 139 106 0 62 247 246 84 8 239 239 94 8 231 231 104 8 85 67 265 216 85 5 256 211 95 4 245 207 105 3 72 288...

Page 34: ...225 8 60 9 55 366 9 237 7 58 3 247 9 195 9 64 0 72 66 391 3 246 8 56 9 262 1 200 7 62 9 77 410 3 254 0 55 7 273 5 204 6 62 1 Table PD 6 SCWF SIWF 22 Economizer Low Capacity 8 800 cfm Entering Water Te...

Page 35: ...0 cfm 66 gpm EnteringWaterTemp EnteringAir 75 F 85 F 95 F EDB EWB Total Sensible Total Sensible Total Sensible F F MBh MBh LWT MBh MBh LWT MBh MBh LWT 62 257 197 84 3 248 193 94 3 238 188 104 2 75 67...

Page 36: ...9 3 63 261 5 188 6 53 3 175 9 160 0 60 6 72 75 277 6 194 2 52 4 184 5 162 8 59 9 80 283 2 196 2 52 1 187 7 163 8 59 7 Table PD 8 SCWF SIWF 25 Economizer Full Capacity 10 000 cfm Entering Water Temp En...

Page 37: ...EDB EWB Total Sensible Total Sensible Total Sensible F F MBh MBh LWT MBh MBh LWT MBh MBh LWT 62 281 234 83 9 270 229 93 8 259 224 103 6 75 67 306 184 84 5 294 179 94 4 281 174 104 3 72 332 133 85 3 3...

Page 38: ...1 60 9 73 489 7 316 0 58 4 331 0 260 1 64 1 72 87 521 5 327 9 57 0 349 3 266 3 63 0 102 547 9 337 9 55 7 365 1 271 7 62 2 Table PD 12 SCWF SIWF 29 Economizer Low Capacity 11 600 cfm Entering Water Tem...

Page 39: ...600 cfm 87 gpm Entering Water Temp Entering Air 75 F 85 F 95 F EDB EWB Total Sensible Total Sensible Total Sensible F F MBh MBh LWT MBh MBh LWT MBh MBh LWT 62 335 266 84 2 323 259 94 1 309 254 104 0...

Page 40: ...61 3 80 526 4 342 5 58 2 355 4 282 6 63 9 72 96 560 6 355 2 56 7 375 4 289 3 62 8 102 571 4 359 3 56 2 381 8 291 5 62 5 32 Ton Table PD 15 SCWF SIWF 32 Economizer Low Capacity 12 800 cfm Entering Wat...

Page 41: ...EDB EWB Total Sensible Total Sensible Total Sensible F F MBh MBh LWT MBh MBh LWT MBh MBh LWT 62 367 317 83 9 352 310 93 8 337 303 103 7 75 67 398 246 84 6 382 240 94 5 365 233 104 3 72 432 175 85 3 4...

Page 42: ...9 53 1 333 5 333 5 60 6 88 544 2 357 0 57 4 365 6 294 8 63 3 72 105 577 1 369 2 56 0 384 6 301 2 62 3 119 599 3 377 5 55 1 397 7 305 6 61 7 Table PD 18 SCWF SIWF 35 Economizer Low Capacity 14 000 cfm...

Page 43: ...000 cfm 105 gpm Entering Water Temp Entering Air 75 F 85 F 95 F EDB EWB Total Sensible Total Sensible Total Sensible F F MBh MBh LWT MBh MBh LWT MBh MBh LWT 62 401 320 84 1 386 313 94 0 369 306 103 9...

Page 44: ...7 235 7 59 0 95 366 9 263 3 52 7 244 3 222 3 60 1 72 114 388 7 270 9 51 8 256 2 226 2 59 5 119 393 6 272 7 51 6 259 0 227 1 59 4 Table PD 20 SCWF SIWF 38 Economizer Full Capacity 15 200 cfm Entering...

Page 45: ...EDB EWB Total Sensible Total Sensible Total Sensible F F MBh MBh LWT MBh MBh LWT MBh MBh LWT 62 434 373 83 9 416 365 93 8 398 357 103 7 75 67 471 290 84 6 452 283 94 5 432 275 104 3 72 511 206 85 3 4...

Page 46: ...1 0 105 712 7 457 3 58 6 479 1 374 9 64 1 72 126 756 0 473 6 57 0 504 7 383 5 63 0 142 782 8 483 8 56 0 520 7 388 9 62 3 Table PD 24 SCWF SIWF 42 Economizer Low Capacity 16 800 cfm Entering Water Temp...

Page 47: ...EDB EWB Total Sensible Total Sensible Total Sensible F F MBh MBh LWT MBh MBh LWT MBh MBh LWT 62 488 403 84 1 469 394 94 1 449 385 104 0 75 67 530 317 84 9 510 309 94 7 488 300 104 6 72 576 231 85 6 5...

Page 48: ...115 761 0 492 1 58 2 511 5 404 5 63 9 72 138 806 5 509 1 56 7 538 2 413 4 62 8 142 813 3 511 6 56 5 542 2 414 8 62 6 46 Ton Table PD 27 SCWF SIWF 46 Economizer Low Capacity 18 400 cfm Entering WaterTe...

Page 49: ...EDB EWB Total Sensible Total Sensible Total Sensible F F MBh MBh LWT MBh MBh LWT MBh MBh LWT 62 517 449 83 8 498 439 93 6 476 429 103 5 75 67 561 348 84 4 540 340 94 3 516 331 104 1 72 609 248 85 1 5...

Page 50: ...535 8 60 9 130 888 9 569 1 58 7 597 7 466 2 64 2 72 156 943 3 589 5 57 1 629 7 477 0 63 1 182 986 2 606 0 55 8 655 5 485 8 62 2 Table PD 30 SCWF SIWF 52 Economizer Low Capacity 20 800 cfm Entering Wat...

Page 51: ...EDB EWB Total Sensible Total Sensible Total Sensible F F MBh MBh LWT MBh MBh LWT MBh MBh LWT 62 596 471 84 1 575 461 94 0 551 450 103 9 75 67 650 376 84 8 626 366 94 7 601 356 104 6 72 707 280 85 5 6...

Page 52: ...59 3 145 628 9 444 0 53 7 419 7 373 6 60 8 72 174 665 8 457 0 52 7 439 8 380 2 60 1 186 678 6 461 5 52 3 447 0 382 5 59 8 Table PD 32 SCWF SIWF 58 Economizer Full Capacity 23 200 cfm Entering WaterTe...

Page 53: ...EDB EWB Total Sensible Total Sensible Total Sensible F F MBh MBh LWT MBh MBh LWT MBh MBh LWT 62 663 571 83 9 637 559 93 8 610 547 103 7 75 67 720 444 84 6 692 433 94 4 662 421 104 3 72 782 316 85 3 7...

Page 54: ...638 2 60 6 163 1043 6 680 9 57 8 701 3 561 3 63 6 72 195 1103 6 703 1 56 3 736 1 573 0 62 5 226 1149 9 720 5 55 2 763 4 582 1 61 8 Table PD 36 SCWF SIWF 65 Economizer Low Capacity 26 000 cfm Entering...

Page 55: ...EDB EWB Total Sensible Total Sensible Total Sensible F F MBh MBh LWT MBh MBh LWT MBh MBh LWT 62 744 609 84 1 715 597 93 9 686 583 103 8 75 67 809 480 84 8 779 468 94 6 746 455 104 5 72 879 351 85 5 8...

Page 56: ...681 6 61 0 180 1118 3 737 1 57 4 751 4 609 6 63 3 72 216 1182 3 760 6 55 9 788 3 621 9 62 3 226 1197 5 766 2 55 6 797 1 624 8 62 1 Table PD 39 SCWF SIWF 72 Economizer Low Capacity 28 000 cfm Entering...

Page 57: ...EDB EWB Total Sensible Total Sensible Total Sensible F F MBh MBh LWT MBh MBh LWT MBh MBh LWT 62 799 690 83 7 768 675 93 6 735 660 103 4 75 67 868 536 84 3 834 522 94 2 798 509 104 0 72 941 381 85 0 9...

Page 58: ...8 703 8 60 7 200 1170 1 766 1 56 7 783 6 631 4 62 8 72 240 1233 4 789 5 55 3 820 2 643 6 61 8 248 1244 3 793 5 55 0 826 5 645 7 61 7 Table PD 42 SCWF SIWF 80 Economizer Low Capacity 29 800 cfm Enterin...

Page 59: ...B EWB Total Sensible Total Sensible Total Sensible F F MBh MBh LWT MBh MBh LWT MBh MBh LWT 62 891 761 83 7 856 746 93 6 819 729 103 4 75 67 966 590 84 3 928 575 94 2 887 559 104 0 72 1049 419 85 0 100...

Page 60: ...242 6 171 7 67 313 6 139 5 302 6 135 2 290 9 130 6 278 4 125 7 265 1 120 6 62 287 3 240 4 277 4 235 9 266 8 231 1 255 4 226 0 243 4 220 5 75 67 313 3 188 7 302 4 184 3 290 7 179 7 278 2 174 8 264 9 16...

Page 61: ...192 0 67 367 8 161 8 355 1 156 6 341 7 151 1 327 5 145 5 312 4 139 5 62 336 5 265 4 324 9 260 1 312 5 254 5 299 4 248 7 285 5 242 5 75 67 367 4 212 3 354 8 207 1 341 4 201 6 327 2 195 9 312 1 189 9 72...

Page 62: ...226 3 67 404 3 181 4 388 9 175 4 372 8 169 2 355 9 162 7 338 2 156 0 62 371 5 320 3 357 6 314 0 343 0 307 3 327 8 300 3 311 9 292 7 75 67 403 9 249 1 388 6 243 1 372 5 236 9 355 6 230 3 337 9 223 6 72...

Page 63: ...240 5 67 453 3 200 0 437 9 193 7 421 4 187 1 403 8 180 2 384 9 172 8 62 415 0 333 7 400 9 327 3 385 6 320 5 369 3 313 3 352 0 305 6 75 67 452 9 265 1 437 6 258 9 421 1 252 2 403 4 245 2 384 6 237 8 72...

Page 64: ...268 6 67 480 9 215 4 463 5 208 6 445 0 201 4 425 4 193 9 404 5 186 0 62 441 7 378 7 425 9 371 6 409 1 364 0 391 4 355 9 372 6 347 1 75 67 480 6 295 0 463 2 288 2 444 7 281 0 425 0 273 4 404 2 265 4 72...

Page 65: ...308 9 67 559 2 249 9 539 0 241 9 517 6 233 6 495 0 224 8 471 1 215 7 62 512 3 434 1 494 0 425 8 474 6 417 0 454 1 407 6 432 6 397 5 75 67 558 7 339 8 538 5 331 8 517 2 323 4 494 6 314 6 470 7 305 4 7...

Page 66: ...393 7 67 719 0 320 1 692 5 309 7 664 9 298 9 636 0 287 7 605 8 276 2 62 657 8 552 9 633 5 542 1 608 4 531 0 582 2 519 4 555 0 507 1 75 67 718 4 433 7 692 0 423 2 664 3 412 3 635 4 401 1 605 3 389 4 72...

Page 67: ...28 5 67 954 6 427 0 917 3 412 4 878 5 397 4 838 1 381 9 796 1 366 0 62 874 6 748 6 840 9 733 7 805 9 718 3 769 5 702 2 731 9 685 6 75 67 953 8 583 7 916 5 569 1 877 8 553 9 837 4 538 3 795 4 522 2 72...

Page 68: ...7 84 0 74 6 80 tons 29800 631 5 79 5 63 1 761 5 83 6 75 9 Based on 60 degree F EAT with a 20 degree F water temperature differance Table PD 53 Steam Heating Capacity 2 psi 5 psi 10 psi Unit Airflow Ca...

Page 69: ...Analog input Airside economizer damper minimum position Analog output Outside air damper actuator Heat Module Option Analog output Generic BAS Option GBAS Binary inputs Demand limit contacts Binary o...

Page 70: ...I module or ventilation override module VOM were field installed the unit configuration will require editing to reflect those options for proper unit operation SERVICE allows servicing or troubleshoot...

Page 71: ...air dampers Closed Heat all stages Off Modulating heat output at 0 vdc Occupied Unoccupied output Deenergized VO relay Energized Exhaust fan field installed Off Exhaust damper field installed Closed...

Page 72: ...nits with a GBAS and is used to reduce electrical consumption at peak load times There are two types of demand limiting 50 and 100 When demand limiting is needed mechanical cooling and heating operati...

Page 73: ...de vanes will close when the supply fan is off Variable Frequency Drive VFD Control Variable frequency drives are driven by a modulating 0 10 vdc signal from the RTM module A pressure transducer measu...

Page 74: ...of cooling will start after the economizer reaches full open Note that the airside economizer will only function freely if ambient conditions are below the enthalpy control settings or below the retur...

Page 75: ...atisfy cooling requirements Heating Hot Water or Steam On units with hot water or steam heating the supply air temperature can be controlled to a heating setpoint during the occupied mode The supply a...

Page 76: ...tback sensor Accessory Model Number Digit 6 J BAYSENS020 This programmable night setback sensor is for use inVAV applications The sensor has a time clock function that provides communication to the se...

Page 77: ...rature setpoint levers for setting cooling blue lever or heating red lever Thermometer to indicate temperatuare in the zone Function status indicator lights SYS ON glows continuously during normal ope...

Page 78: ...temperature sensing in the zone A timed override button to move an Integrated Comfort System or a building management system from unoccupied to occupied mode Setpoint thumbwheel for local setpoint ad...

Page 79: ...SIRF 20 25 29 30 35 40 50 60 SCWF SIWF 20 25 29 32 35 38 42 46 52 58 65 72 80 10 2 1 3 2 1 15 1 1 3 3 4 Table ED 2 SCWF SIWF Compressor Electrical Data 200V 460V 575V HP RLA LRA RLA LRA RLA LRA 10 33...

Page 80: ...7 Note Electric heat amperage should not be considered when determining minimum circuit ampacity The current of the unit in the heating mode will not exceed the current of the unit in the cooling mod...

Page 81: ...Dimensions and Weights PKG PRC002 EN 81 Self Contained 20 38 Tons 20 38Ton Self Contained...

Page 82: ...Dimensions and Weights PKG PRC002 EN 82 40 80Ton Self Contained Self Contained 40 80 Ton 82...

Page 83: ...C D SXWF 20 25 30 3 8 26 1 8 21 1 4 25 3 4 SXRF 20 SXWF 29 32 31 7 8 23 1 2 23 1 8 20 3 8 SXRF 25 29 SXWF 35 38 30 1 2 26 1 8 21 1 4 25 3 4 SXRF 30 35 SXWF 42 80 43 1 8 33 1 2 28 7 8 34 1 2 SXRF 40 6...

Page 84: ...CCRC CIRC 35 40 1781 3321 2235 CCRC CIRC 50 60 1781 4470 2235 Air Cooled Condenser CCRC CIRC 20 and 29 CCRC CIRC 35 and 40 CCRC CIRC 50 and 60 AC Optional Low Ambient Damper OneDamperPerCircuit Refri...

Page 85: ...it E F G H J K L M N CCRC CIRC20 32 1699 365 470 629 737 16 29 16 29 CCRC CIRC35 40 1699 365 470 629 737 16 29 22 35 CCRC CIRC 50 1699 365 470 629 737 16 29 22 41 CCRC CIRC 60 1699 365 470 629 737 22...

Page 86: ...8 105 1 4 18 13 1 4 3 22 1 8 6 3 8 5 3 8 4 3 8 1 1 4 Piping Locations For Steam Coils Metric mm A B C D E F G H J K L M N Unit Sizes 20 38 1534 2105 457 568 76 470 98 127 111 32 Unit Sizes 42 80 1851...

Page 87: ...119 7 8 390 lbs Unit Sizes 42 80 Std 80 3 8 28 5 8 119 7 8 540 lbs Ext 80 3 8 45 119 7 8 705 lbs Plenum Dimensions Metric mm A B C Weight Low 1648 625 2435 147 4 kg Unit Sizes 20 38 Std 1648 822 2435...

Page 88: ...Dimensions and Weights PKG PRC002 EN 88 Airside Economizer Airside Economizer...

Page 89: ...2 40 SXRF 57 3 8 86 1 2 13 1 4 104 3 8 8 7 8 94 1 8 63 1 2 28 1 8 26 6 7 8 15 26 24 3 4 20 3 8 63 1 2 46 SXWF 50 SXRF 57 3 8 86 1 2 13 1 4 104 3 8 8 7 8 96 5 8 63 1 2 52 37 1 2 1 7 8 9 1 4 37 1 2 19 2...

Page 90: ...ilities 70 mm 114 mm Zone Temperature Sensor W Timed Override Buttons BAYSENS013 70 mm 114 mm Dual Setpoint Manual Automatic Changeover Sensor With System Function Lights BAYSENS010 70 mm 114 mm Zone...

Page 91: ...Zone Sensors 70 mm 114 mm Zone Temperature Sensor Only BAYSENS017 Single Setpoint Sensor With System Function Lights BAYSENS021 70 mm 114 mm Programmable Night Setback Sensor BAYSENS019B 140 mm 95 mm...

Page 92: ...on and waterside component service Right 9 in 229 mm Non VFD w open return 18 in 457 mm Non VFD w ducted return 24 in 610 mm w VFD 7 5 to 20 HP 36 in 914 mm w VFD 25 to 50 HP Inlet 18 in 457 mm Provid...

Page 93: ...32mm A D B C F E G H 96 2132mm 48 1066mm Control Panel 96 2132mm 48 1066mm C B D A Top View CCRC CIRC 20 29 Top View CCRC CIRC 35 40 Service Clearances Remote Air Cooled Condensers Models CCRC CIRC To...

Page 94: ...0 1510 500 225 190 85 390 175 460 210 30 3370 1530 500 225 280 130 505 230 460 210 35 3470 1575 500 225 280 130 505 230 460 210 40 4410 2000 640 290 255 115 505 230 600 270 50 4980 2260 700 315 335 15...

Page 95: ...Two refrigerant circuits shall be piped to the unit s exterior The refrigerant piping includes filter driers for field installation sight glasses distributors thermal expansion valves with adjustable...

Page 96: ...include an integral subcooling circuit for each circuit All necessary controls to run unit fans shall be factory installed The control panel shall include fan motor contactors terminal block connecti...

Page 97: ...to accelerate or decelerate as required to maintain the supply static pressure setpoint Supply AirTemperature ControlWith Variable Frequency Drive with Bypass Manual bypass control provides full nomin...

Page 98: ...the first stage of cooling in occupied or unoccupied mode and when ambient conditions are favorable for economizing Inherent in the unit controller is the ability to suppress the setpoint below the no...

Page 99: ...minum fins positioned continuously across the entire coil width not exceeding 12 fins per inch The coil casing is 16 gauge steel Coil performance is rated at a maximum working pressure of 200 psig in...

Page 100: ...unit sizes 20 38 tons the low height plenum is 24 5 8 inches 625 mm and the standard height plenum is 32 3 8 inches 822 mm On unit sizes 42 80 tons the low height plenum is 21 1 8 inches 537 mm and t...

Page 101: ...fications without notice Literature Order Number PKG PRC002 EN File Number PL UN PKG PRC002 EN 1201 Supersedes PKG PRC002 EN 01 01 Stocking Location La Crosse Inland TheTrane Company A Division of Ame...

Reviews: