18
MS-SVN056C-EN
Cassette Unit Installation
Distribution ductwork installation
Model 18 to 24 Series A = 160mm; Series B = 75mm
Model 36 to 60 Series A = 160mm; Series B = 95mm
Single duct connection
Ductwork air volume is approximately 300-360m3/h - Model 18 to 24
Ductwork air volume is approximately 400-640m3/h - Model 36 to 60
Maximum duct length is 2m.
In the case of double duct connection, the original opening for outgoing air with the same piping direction, must
be sealed.
Double duct connection
Ductwork air volume is approximately 200-260m3/h - Model 18 to 24
Ductwork air volume is approximately 300-500m3/h - Model 36 to 60
Maximum duct length is 1.5m for a single duct.
The original opening for outgoing air with the same piping direction, must be sealed.
80mm
80mm
Ø75mm
MODLE (18-60)
Fresh air
intake
Distribution duct
Distribution
duct
Distribution
duct
Distribution duct
Fresh air
One way
Two ways
Summary of Contents for 2MCC05-C
Page 24: ...24 MS SVN056C EN Concealed Unit Installation Performance Curves...
Page 25: ...MS SVN056C EN 25 Concealed Unit Installation...
Page 71: ...MS SVN056C EN 71 Wiring Diagrams Outdoor Unit Cooling Only 4TTK05 D 36K 3 Phase...
Page 72: ...72 MS SVN056C EN Wiring Diagrams Outdoor Unit Cooling Only 4TTK05 D 48K 3 Phase...
Page 73: ...MS SVN056C EN 73 Wiring Diagrams Outdoor Unit Cooling Only 4TTK05 D 60K 3 Phase...
Page 74: ...74 MS SVN056C EN Wiring Diagrams Outdoor Unit Cooling Only Heat Pump 4TWK05 D 36K 3 Phase...
Page 75: ...MS SVN056C EN 75 Wiring Diagrams Outdoor Unit Cooling Only Heat Pump 4TWK05 D 48K 3 Phase...
Page 76: ...76 MS SVN056C EN Wiring Diagrams Outdoor Unit Cooling Only Heat Pump 4TWK05 D 60K 3 Phase...
Page 78: ......
Page 79: ......