36
MS-SVN056C-EN
Outdoor Unit Installation
Procedure for pipe connection
1. Measure the required length of tube connection and proceed as follows. First
connect the indoor unit; then connect the outdoor unit.
–
Fold the pipe appropriately. Do not twist the tube.
–
Apply refrigerant oil on the surface of the flared pipe and on the union nuts; using hands, apply
tightening torque for 3 to 4 turns, before using the wrench.
–
Employ two open-end wrenches simultaneously to connect or disconnect piping
•
Outdoor unit service valves must be totally closed (original state). In order to connect them, loosen the
nuts and connect flared tubes in a timing not to exceed 5 minutes. If nuts remain loose during extended
time, it could lead to dust and other debris entering the system and consequently causing a system
malfunction. Therefore, before the final connection, purge air from the refrigerant line.
•
Purge air after connecting the refrigerant line to both indoor unit and outdoor unit. Tighten nuts on the
service valves.
•
Fold the thin-walled connecting tube.
–
Cut the insulation material insulating material all over the pipe on the section to be folded.
–
Expose the pipe. Proceed to fold it. Once folded, cover it completely with insulating material
–
In order to prevent pipe from deforming or twisting, fold it at a suitable radius.
Tube
Diameter
Tightening Torque
Flare dimension (A)
(mm/inch)
Flaring
Min.
Max.
φ
6.4
14.2 + 17.2 N.m.
(144-176 kgf.cm)
8.3/0.3
8.3/0.3
φ
9.5
32.7 + 39.9 N.M
(333-407 kgf.cm)
12.4/0.48
12.4/0.48
φ
12.7
49.5 + 60.3 N.M
(504-616 kgf.cm)
15.4/0.6
15.8/0.6
φ
15.9
61.8 + 75.4 N.M
(630-770 kgf.cm)
18.6/0.7
19/0.74
φ
19.1
97.2 + 118.6 N.M
(990-1210 kgf.cm)
22.09/0.9
23.3/0.91
φ
22
109.5 + 133.7 N.M
(1117-1364 kgf.cm)
27/1.06
27.3/1.07
R0.4~0.8
45 °
±2
90 °
± 4
A
Fold pipe using thumbs at a
minimum radius of 100mm/3.94in
use frozen oil
endings must
be straight
Summary of Contents for 2MCC05-C
Page 24: ...24 MS SVN056C EN Concealed Unit Installation Performance Curves...
Page 25: ...MS SVN056C EN 25 Concealed Unit Installation...
Page 71: ...MS SVN056C EN 71 Wiring Diagrams Outdoor Unit Cooling Only 4TTK05 D 36K 3 Phase...
Page 72: ...72 MS SVN056C EN Wiring Diagrams Outdoor Unit Cooling Only 4TTK05 D 48K 3 Phase...
Page 73: ...MS SVN056C EN 73 Wiring Diagrams Outdoor Unit Cooling Only 4TTK05 D 60K 3 Phase...
Page 74: ...74 MS SVN056C EN Wiring Diagrams Outdoor Unit Cooling Only Heat Pump 4TWK05 D 36K 3 Phase...
Page 75: ...MS SVN056C EN 75 Wiring Diagrams Outdoor Unit Cooling Only Heat Pump 4TWK05 D 48K 3 Phase...
Page 76: ...76 MS SVN056C EN Wiring Diagrams Outdoor Unit Cooling Only Heat Pump 4TWK05 D 60K 3 Phase...
Page 78: ......
Page 79: ......