Causes of faults and remedies
TR-Electronic GmbH 2014, All Rights Reserved
Printed in the Federal Republic of Germany
Page 182 of 183
TR - ELA - BA - DGB - 0023 - 06
05/04/2018
10.3 Position Status
Additionally to the current position by means of bit 2
0
of the status register it is
reported whether the magnets are in the permissible range.
See also:
● Assembly, from page 114
● Object 0x04, Assembly, from page 124
● Attribute 111, Position Status, page 154
Bit
Fault
Cause
Remedy
0
Bit 0 = 1
Measuring
system
has
detected no magnet.
Slide magnet into the permissible
measuring range.
The number of magnets
defined in “Attribute 110,
not agree with the operated
number of magnets.
Verify the programmed number of magnets under
“Object 0x23, Position Sensor” with the operated
number.
10.4 Other faults
Fault
Cause
Remedy
Position skips
of the measuring
system
Strong vibrations
Vibrations, impacts and shocks, e.g. on presses, are
dampened with "shock modules". If the error recurs
despite these measures, the measuring system must
be replaced.
Electrical faults
EMC
Perhaps isolated flanges and couplings made of
plastic help against electrical faults, as well as
cables with twisted pair wires for data and supply.
Shielding and wire routing must be performed
according to the specification.