Parameterization
TR-Electronic GmbH 2014, All Rights Reserved
Printed in the Federal Republic of Germany
Page 146 of 183
TR - ELA - BA - DGB - 0023 - 06
05/04/2018
7.4.3.20 Attribute 44, Alarms
An alarm is set if a malfunction bit is set to TRUE (high). The alarm remains active
until the device is able to provide an accurate position value and the alarm is cleared
by a restart or a reset.
WORD, read only
Bit
Description
FALSE (0)
TRUE (1)
0
Position error
No
Yes
1…11
Reserved or not supported
-
-
12
EEPROM error
No
Yes
13…15
Reserved
-
-
Corresponding measures in case of an error see chapter “Causes of faults and
remedies
Connection path,
Packed EPATH
with 8 bit class
0x20
0x23
0x24
0x01
0x30
0x2C
Logical Type
= Class
Class #23
Logical Type
= Instance
Instance #1
Logical Type
=Attr.-ID
Attr.-ID #44
7.4.3.21 Attribute 45, Supported Alarms
Supported Alarms
displays the alarms supported by the measuring system.
WORD, read only
Bit
Description
FALSE (0)
TRUE (1)
0
Position error
-
supported
1…11
Reserved or not supported
-
-
12
EEPROM error
-
supported
13…15
Reserved
-
-
Connection path,
Packed EPATH
with 8 bit class
0x20
0x23
0x24
0x01
0x30
0x2D
Logical Type
= Class
Class #23
Logical Type
= Instance
Instance #1
Logical Type
=Attr.-ID
Attr.-ID #45