7.4.3.39 Attribute 115, Temperature Low Limit (optional)
Temperature Low Limit
defines the minimum value of the temperature with the
unit that is defined in “Attribute 114, Temperature Value Format” it is standardly °C. If
this value falls below in “Attribute 47, Warnings” the depending warn bit (13) is set to
high.
INT, Default: - 20 °C
Temperature Low Limit
Byte 0
Byte 1
2
7
up to 2
0
2
15
up to 2
8
Connection path,
Packed EPATH
with 8 bit class
0x20
0x23
0x24
0x01
0x30
0x73
Logical Type
= Class
Class #23
Logical Type
= Instance
Instance #1
Logical Type
=Attr.-ID
Attr.-ID #115
To save this attribute permanently the attribute 112
Accept Parameter
or service
code 0x16
save
must be executed.
7.4.3.40 Attribute 116, Temperature High Limit (optional)
Temperature High Limit
defines the maximum value of the temperature with the
unit that is defined in “Attribute 114, Temperature Value Format” it is standardly °C. If
this value is exceeded in “Attribute 47, Warnings” the depending warn bit (14) is set to
high.
INT, Default: + 85 °C
Temperature High Limit
Byte 0
Byte 1
2
7
up to 2
0
2
15
up to 2
8
Connection path,
Packed EPATH
with 8 bit class
0x20
0x23
0x24
0x01
0x30
0x74
Logical Type
= Class
Class #23
Logical Type
= Instance
Instance #1
Logical Type
=Attr.-ID
Attr.-ID #116
To save this attribute permanently the attribute 112
Accept Parameter
or service
code 0x16
save
must be executed.