Important: Photocells notes
•
The control unit has a power supply connection for a 24V a.c. photocell (PHC):
supply PHC-transmitter: terminals 40/41 / supply PHC-receiver: terminals 40/43
Note: in „gate closed“ position the terminals 40/41 get switched into energy saving mode (no current) (only, if
no TX 310 system is used) !
• The contact has to be closed when using powered and positioned photocells (opening contact).
Connection of the photocell contact: terminals 46/47
• When using two pairs of photocells please do not
install both photocell transmitters/receivers on the
same side (to eleminate interference between both) !
Exception: photocells with SYNC function allow the
installation of both photocell transmitters/receivers on
the same side without causing interference to each
other.
• Photocell self-test function:
The control board is equipped with a self-test function for the connected photocell. ith an
opening impulse (switch or button) the transmitter of the photocell is switched off for a short time in gate position „closed”.
Thus the photocell receiver interrupts the contact 46/47 - the control board verifies the function of the photocell receiver.
this short interruption at the photocell input is not carried out, the control board reports an error.
The deactivation of the
self-test function is only allowed if the safety installations correspond to the category 3 !
• The exact function of the photocells depend on the programming of the control unit.
Photocell function please see
menu point SAFETY / photocell function or photocell with pause time
• You will find detailed information in the corresponding photocell manual.
Standard:
transmitter 1
receiver1
receiver 2
transmitter 2
with SYNC-Function:
transmitter 1
receiver 1
transmitter 2
receiver 2
Safety
Connections and adjustments
G
Photocells
(contact: terminals X1: 46/47)
Safety
ACTIVE:
to be selected, if photocell should be triggered.
NOT ACTIVE
to be selected, if photocell should not be triggered.