TF type(1:1 only)
・ Diversity
- 80% - 100%
・ Overview
For example schematic of system ;
3. Operating conditions
Ensure the "Coil on Air" temperature is within the range of the Dx-coil design guideline.
OA Outdoor Air
SA
Supply Air
CA Coil on Air
(After Heat Recovery Exchanger)
RA Return Air
EA
Exhaust Air
AHU
Note: If intake air temperature is out of range of the specification, the damage for the
system may be caused.
Outdoor unit Refer to specification of outdoor unit
15 - 24 ̊C WB
15 - 32 ̊C WB
*Outdoor unit model or select cooling only mode with HP model
**Outdoor/Suction air temp. 46 - 52 °C(DB) is also available but Temporaty operatable.
TF or DDC
TA or DDC
Control
HP(TA)
(Heating & Cooling)
Cooling Only*
Pattern A
Pattern B
HP(TF)
(Heating & Cooling)
(18 - 43 ̊C DB)
Heating mode "Coil on Air" temp.
12 - 28 ̊C DB
(Pull down to 7 ̊C)
-10 - 15 ̊C DB
---
---
Cooling mode "Coil on Air" temp.
15 - 24 ̊C WB
10 - 32 ̊C WB
(18 - 32 ̊C DB)
(19 - 46 ̊C** DB)
(18 - 32 ̊C DB)