6.3 Control Input / Output Details
-Analog Input functions -
Input
Name
Description
TA DDC TF
AI1
FAN interlock
FAN interlocking control by external input
Analog Input 1 (4 - 20 mA)
・FAN mode is switched by external 4 - 20 mA input.
・Both FAN control with 4 - 20 mA input and FAN mode change with remote controller are valid, but boost
priority is given.
・The FAN priority control is switched by the DN setting of [4A0].
0000: Default (no change in FAN mode by 4 - 20 mA input)
0001: FAN control by 4 - 20 mA input, but priority is given to FAN control from the outdoor unit
0002: FAN control 4 - 20 mA input with priority
・The FAN mode switching threshold value for 4 - 20 mA input can be changed in the DN setting
* The change in FAN speed with 4 - 20 mA input is also reflected in the 0 - 10 V output of AO1 / AO1.
AI2
Nothing
Cannot be used.
Analog Input 2 (4 - 20 mA)
✓
✓
✓
‐
‐
‐
✓ :Available × : Prohibition