7.5 DX COIL Guideline HP
- Guideline HP -
HP
26
28
30
32
34
36
38
40
42
Std.
11,210
12,060
12,900
14,400
14,590
15,600
16,280
16,800
17,970
Min.
8,970
9,650
10,320
11,520
11,670
12,480
13,030
13,440
14,380
Max.
13,530
14,550
15,570
17,280
17,610
18,720
19,650
21,160
21,690
Min.
11,050
11,900
12,750
13,600
14,450
15,300
16,150
17,000
17,850
Max.
14,950
16,100
17,250
18,400
19,550
20,700
21,850
23,000
24,150
Copper Tube Dia. (mm)
Ø12.7, Ø9.52, Ø8.00 (Recommended Ø9.52 or Less)
Max. Capacity (kW)
72.8
80.0
84.0
90.0
95.4
101.0
106.4
112.0
120.0
Coil on Air Temp.
15 - 24°CWB (18 - 32°CDB)
Evaporating Temp.
6.5°C
Superheat
6K
27°CDB / 19°CWB
Max. Capacity (kW)
81.5
90.0
94.5
100.0
106.0
113.0
119.0
126.0
135.0
Coil on Air Temp.
12 - 28°CWB
Condensating Temp.
52°C
Sub Cooling
4K
20°CDB
HP
44
46
48
50
52
54
56
58
60
Std.
18,820
19,660
20,400
21,350
22,200
23,400
23,890
24,730
25,200
Min.
15,050
15,730
16,320
17,080
17,760
18,720
19,110
19,780
20,160
Max.
22,710
23,730
24,480
25,760
26,780
28,080
28,820
29,840
30,240
Min.
18,700
19,550
20,400
21,250
22,100
22,950
23,800
24,650
25,500
Max.
25,300
26,450
27,600
28,750
29,900
31,050
32,200
33,350
34,500
Copper Tube Dia. (mm)
Ø12.7, Ø9.52, Ø8.00 (Recommended Ø9.52 or Less)
Max. Capacity (kW)
125.0
130.0
140.4
140.4
145.8
151.2
160.0
162.4
168.0
Coil on Air Temp.
15 - 24°CWB (18 - 32°CDB)
Evaporating Temp.
6.5°C
Superheat
6K
27°CDB / 19°CWB
Max. Capacity (kW)
140.0
145.0
156.0
156.0
162.0
168.0
180.0
182.0
189.0
Coil on Air Temp.
12 - 28°CWB
Condensating Temp.
52°C
Sub Cooling
4K
20°CDB
AHU Air
Flow rate
(m3/hr)
H
ea
tin
g
Air Suction Temp.
(Design temp)
AHU Air
Flow rate
(m3/hr)
DX Coil Internal
volume (cc)
C
oo
lin
g
Air Suction Temp.
(Design temp)
DX Coil Internal
volume (cc)
C
oo
lin
g
Air Suction Temp.
(Design temp)
H
ea
tin
g
Air Suction Temp.
(Design temp)
P24
Summary of Contents for RBM-A101UPVA-E
Page 21: ...P19 ...
Page 45: ...9 Cable specifications P43 ...
Page 46: ...10 Modbus setting method P44 ...
Page 50: ...12 Dx coil Controller Dx valve kit Dimensions P48 ...
Page 51: ...12 Dx coil Controller Dx valve kit Dimensions P49 ...
Page 52: ...13 Wiring Diagram P50 ...
Page 53: ...P51 ...
Page 58: ...VRF Dx coil interface Design Guideline May 2022 Third Edition DG003 03 ...