7.6 DX COIL Guideline CO Pattern A
- Guideline Cooling Only Pattern A -
HP
26
28
30
32
34
36
38
40
42
Std.
11,210
12,060
12,900
14,400
14,590
15,600
16,280
16,800
17,970
Min.
Max.
Min.
11,050
11,900
12,750
13,600
14,450
15,300
16,150
17,000
17,850
Max.
20,800
22,400
24,000
25,600
27,200
28,800
30,400
32,000
33,600
Copper Tube Dia. (mm)
Ø12.7, Ø9.52, Ø8.00 (Recommended Ø9.52 or Less)
Max. Capacity (kW)
72.8
80.0
84.0
90.0
95.4
101.0
106.4
112.0
120.0
Coil on Air Temp.
15 - 24°CWB (18 - 32°CDB)
Evaporating Temp.
6.5°C
Superheat
6K
27°CDB / 19°CWB
Max. Capacity (kW)
-
-
-
-
-
-
-
-
-
Coil on Air Temp.
-
Condensating Temp.
-
Sub Cooling
-
-
HP
44
46
48
50
52
54
56
58
60
Std.
18,820
19,660
20,400
21,350
22,200
23,400
23,890
24,730
25,200
Min.
Max.
Min.
18,700
19,550
20,400
21,250
22,100
22,950
23,800
24,650
25,500
Max.
35,200
36,800
38,400
40,000
41,600
43,200
44,800
46,400
48,000
Copper Tube Dia. (mm)
Ø12.7, Ø9.52, Ø8.00 (Recommended Ø9.52 or Less)
Max. Capacity (kW)
125.0
130.0
140.4
140.4
145.8
151.2
160.0
162.4
168.0
Coil on Air Temp.
15 - 24°CWB (18 - 32°CDB)
Evaporating Temp.
6.5°C
Superheat
6K
27°CDB / 19°CWB
Max. Capacity (kW)
-
-
-
-
-
-
-
-
-
Coil on Air Temp.
-
Condensating Temp.
-
Sub Cooling
-
-
AHU Air
Flow rate
(m3/hr)
No restriction
No restriction
No restriction
No restriction
Air Suction Temp.
(Design temp)
H
ea
tin
g
Air Suction Temp.
(Design temp)
DX Coil Internal
volume (cc)
C
oo
lin
g
Air Suction Temp.
(Design temp)
H
ea
tin
g
Air Suction Temp.
(Design temp)
AHU Air
Flow rate
(m3/hr)
DX Coil Internal
volume (cc)
C
oo
lin
g
P28
Summary of Contents for RBM-A101UPVA-E
Page 21: ...P19 ...
Page 45: ...9 Cable specifications P43 ...
Page 46: ...10 Modbus setting method P44 ...
Page 50: ...12 Dx coil Controller Dx valve kit Dimensions P48 ...
Page 51: ...12 Dx coil Controller Dx valve kit Dimensions P49 ...
Page 52: ...13 Wiring Diagram P50 ...
Page 53: ...P51 ...
Page 58: ...VRF Dx coil interface Design Guideline May 2022 Third Edition DG003 03 ...