7.7 DX COIL Guideline CO Pattern B
- Guideline Cooling Only Pattern B -
HP
62
64
66
68
70
72
74
76
78
Std.
26,420
27,270
28,110
28,950
29,800
30,640
31,490
32,330
33,180
Min.
Max.
Min.
13,950
14,400
14,850
15,300
15,750
16,200
16,650
17,100
17,550
Max.
31,000
32,000
33,000
34,000
35,000
36,000
37,000
38,000
39,000
Copper Tube Dia. (mm)
Ø12.7, Ø9.52, Ø8.00 (Recommended Ø9.52 or Less)
Max. Capacity (kW)
175.0
180.0
185.4
190.8
196.2
202.0
207.2
212.8
218.4
Coil on Air Temp.
15 - 32°CWB (18 - 43°CDB)
Evaporating Temp.
6.5°C
Superheat
6K
33°CDB / 28°CWB
Max. Capacity (kW)
-
-
-
-
-
-
-
-
-
Coil on Air Temp.
-
Condensating Temp.
-
Sub Cooling
-
-
HP
80
82
84
86
88
90
92
94
96
Std.
34,020
34,870
35,710
36,560
37,400
38,250
39,090
39,940
40,780
Min.
Max.
Min.
18,000
18,450
18,900
19,350
19,800
20,250
20,700
21,150
21,600
Max.
40,000
41,000
42,000
43,000
44,000
45,000
46,000
47,000
48,000
Copper Tube Dia. (mm)
Ø12.7, Ø9.52, Ø8.00 (Recommended Ø9.52 or Less)
Max. Capacity (kW)
224.0
230.4
240.0
241.2
246.6
252.0
257.6
263.2
270.0
Coil on Air Temp.
15 - 32°CWB (18 - 43°CDB)
Evaporating Temp.
6.5°C
Superheat
6K
33°CDB / 28°CWB
Max. Capacity (kW)
-
-
-
-
-
-
-
-
-
Coil on Air Temp.
-
Condensating Temp.
-
Sub Cooling
-
-
DX Coil Internal
volume (cc)
C
oo
lin
g
Air Suction Temp.
(Design temp)
H
ea
tin
g
Air Suction Temp.
(Design temp)
No restriction
No restriction
No restriction
No restriction
AHU Air
Flow rate
(m3/hr)
AHU Air
Flow rate
(m3/hr)
DX Coil Internal
volume (cc)
C
oo
lin
g
Air Suction Temp.
(Design temp)
H
ea
tin
g
Air Suction Temp.
(Design temp)
P33
Summary of Contents for RBM-A101UPVA-E
Page 21: ...P19 ...
Page 45: ...9 Cable specifications P43 ...
Page 46: ...10 Modbus setting method P44 ...
Page 50: ...12 Dx coil Controller Dx valve kit Dimensions P48 ...
Page 51: ...12 Dx coil Controller Dx valve kit Dimensions P49 ...
Page 52: ...13 Wiring Diagram P50 ...
Page 53: ...P51 ...
Page 58: ...VRF Dx coil interface Design Guideline May 2022 Third Edition DG003 03 ...