7.8 DX COIL Guideline TF
- Guideline TF -
HP
26
28
30
32
34
36
38
40
Max.
-
6,040
-
6,910
-
7,780
-
8,650
Mid
-
5,070
-
5,790
-
6,510
-
7,240
Low
-
4,200
-
4,800
-
5,400
-
6,000
Min.
-
6,020
-
6,880
-
7,740
-
8,600
Max.
-
12,320
-
14,080
-
15,840
-
17,600
Copper Tube Dia. (mm)
Ø12.7, Ø9.52, Ø8.00 (Recommended Ø9.52 or Less)
Max. Capacity (kW)
-
80.0
-
90.0
-
101.0
-
112.0
Coil on Air Temp.
10 - 32°CWB (19 - 46°CDB)**
Evaporating Temp.
6.5°C
Superheat
6K
33°CDB / 28°CWB
Max. Capacity (kW)
-
90.0
-
100.0
-
113.0
-
126.0
Coil on Air Temp.
-10 - 15°CWB
Condensating Temp.
52°C
Sub Cooling
4K
0°CDB
**Outdoor/Suction air temp. 46 - 52 °C(DB) is also available but Temporaty operatable.
H
ea
tin
g
Air Suction Temp.
(Design temp)
AHU Air
Flow rate
(m3/hr)
DX Coil Internal
volume (cc)
C
oo
lin
g
Air Suction Temp.
(Design temp)
P36
Summary of Contents for RBM-A101UPVA-E
Page 21: ...P19 ...
Page 45: ...9 Cable specifications P43 ...
Page 46: ...10 Modbus setting method P44 ...
Page 50: ...12 Dx coil Controller Dx valve kit Dimensions P48 ...
Page 51: ...12 Dx coil Controller Dx valve kit Dimensions P49 ...
Page 52: ...13 Wiring Diagram P50 ...
Page 53: ...P51 ...
Page 58: ...VRF Dx coil interface Design Guideline May 2022 Third Edition DG003 03 ...