11. Function code (DN code)
▼ Function CODE No.(DN code) table (setting by wired remote controller)
DN
Item
Description
Default(at shipment)
01
Filter display delay timer
0000: None
0001: 150H
0000: None
0002: 2500H
0003: 5000H
0004: 10000H
02
Dirty state of filter
0000: Standard
0000: Standard
0001: High degree of dirt (Half of standard time)
04
Specific indoor unit priority 0000: No priority
0001: Priority
0000: No priority
0F
Cooling only
0000: Heat Pump
0000: Heat Pump
0001: Cooling only ( No display of [AUTO], [HEAT] )
10
Type
0055: Dx-coil Interface
0055: Dx-coil Interface
11
Indoor unit capacity
0000: Unfixed
0000: Unfixed
0021
0023
0024
0025
0026
0027
0028
0031
8HP
10HP
12HP
14HP
16HP
18HP
20HP
24HP
0047
0035
0048
0037
0049
0039
28HP
32HP
34HP
36HP
38HP
40HP
12
Line address
0001: No.1 unit
to
0030: No.30 unit
0000: Unfixed
13
Indoor unit address
0001: No.1 unit
to
0064: No.64 unit
0099: Unfixed
28
Automatic restart of
0000: None
0001: Restart
0000: None
power failure
33
Temperature unit select 0000:
°
C
0001:
°
F
0000:
°
C
60
Timer setting
0000: Available(can be performed)
0000: Available
(by Wired remote controller)
0001: Unavailable(cannot be performed)
92
Fan trouble input
0000: Operation stopped
0000: Operation stopped
release condition
0001: Release signal received
4AE Dx-coil PMV kit type setting0001: RBMーA101UPVA-E
Setting depending on HP
0002: RBM-A201UPVAーE
(Horse Power)
P47
Summary of Contents for RBM-A101UPVA-E
Page 21: ...P19 ...
Page 45: ...9 Cable specifications P43 ...
Page 46: ...10 Modbus setting method P44 ...
Page 50: ...12 Dx coil Controller Dx valve kit Dimensions P48 ...
Page 51: ...12 Dx coil Controller Dx valve kit Dimensions P49 ...
Page 52: ...13 Wiring Diagram P50 ...
Page 53: ...P51 ...
Page 58: ...VRF Dx coil interface Design Guideline May 2022 Third Edition DG003 03 ...