– 92 –
9-3. Address Setup (Manual Setting from Remote Controller)
(Ex
a
mple of 2-line
s
wiring)
(
S
olid line: Wiring, Broken line: Refriger
a
nt pipe)
For the
ab
ove ex
a
mple, perform
s
etting
b
y
connecting
s
ingly the wired remote controller
witho
u
t remote controller inter-
u
nit wire.
Gro
u
p
a
ddre
ss
Individ
ua
l : 0000
He
a
der
u
nit : 0001
Follower
u
nit : 0002
In c
as
e of gro
u
p control
O
u
tdoor
Indoor
A B
A B
1 2 3
Indoor
A B
1 2 3
Indoor
A B
1 2 3
Indoor
A B
1 2 3
1 2 3
O
u
tdoor
1 2 3
Remote controller
Line
a
ddre
ss
→
1
Indoor
u
nit
a
ddre
ss
→
1
Gro
u
p
a
ddre
ss
→
1
1
2
2
1
3
2
2
1
2
2
2
2
Indoor
A B
1 2 3
In case that addresses of the indoor units will be
determined prior to piping work after wiring work
• Set an indoor unit per a remote controller.
• Turn on power supply.
<Procedure>
1
Push the [
MENU] button to
display the menu screen.
2
Push and hold the [
MENU]
button and the [
] button
at the same time to display the
“Field setting menu”.
→
Push and hold the buttons for
more than 4 seconds.
(Line address)
→
Move the cursor to select “Code(DN)” with the “
<
<” [
F1
F1] button, then set “
0012
” with the
[
] / [
] button.
→
Move the cursor to select “Data” with the “
>
>” [
F2
F2] button, then set
Line address
“Data” with the [
] / [
] button.
4
Push the [
MENU] button to set the other Code(DN) and Data. After “Continue?” is
displayed on the screen, push the “
Ye
s
Yes” [
F1
F1] button.
(Indoor address)
→
Move the cursor to select “Code(DN)” with the “
<
<” [
F1
F1] button, then set “
0013
” with the
[
] / [
] button.
→
Move the cursor to select “Data” with the “
>
>” [
F2
F2] button, then set
Indoor address
“Data” with the [
] / [
] button.
5
Push the [
MENU] button to set the other Code(DN) and Data. After “Continue?” is
displayed on the screen, push the “
Ye
s
Yes” [
F1
F1] button.
(Group address)
→
Move the cursor to select “Code(DN)” with the “
<
<” [
F1
F1] button, then set “
0014
” with the
[
] / [
] button.
→
Move the cursor to select “Data” with the “
>
>” [
F2
F2] button, then set “0001” to Header
unit, and “0002” to Follower unit with the [
] / [
] button.
6
Push the [
MENU] button to set the other Code(DN) and Data. After “Continue?” is
displayed on the screen, push the “
No
No” [
F2
F2] button to finish the setting
operation.
“ Setting” appears on the screen for a while, then the screen returns to the “Field setting
menu” screen.
3
Push the [
] / [
] button to select
“7. DN setting” on the “Field setting menu”
screen, then push the “
S
et
Set” [
F2
F2] button.
→
The fan and louver of the indoor unit operate.
When the group control is used, the fan and louver
of the selected indoor unit operate.