– 82 –
8-1-6. Monitor Function of Remote Controller Switch
Calling of sensor temperature display
The sensor temperature or operational status of
indoor unit, outdoor unit, or remote controller can be
monitored.
Monitor function
Code
00
Data
0024
Return
*
Display and the contents
- - - - : Sensor function is not available.
0000 : Normal
0001 : Sensor has been used for 5 years.
0002 : Sensor trouble or exceeding the life of the
product for sensor
000
3
: Sensor is detecting refrigerant leak
Indoor unit data
Code
Data name
01
Room temperature (remote controller)
02
Indoor unit intake air temperature (TA)
0
3
Indoor unit heat exchanger (coil)
temperature (TCJ)
04
Indoor unit heat exchanger (coil)
temperature (TC)
F
3
Indoor unit fan cumulative operating hours
(x1 h)
E2
Indoor unit refrigerant leak detection sensor
output
*
Outdoor unit data
Code
Data name
60
Outdoor unit heat exchanger (coil)
temperature (TE)
61
Outside air temperature (TO)
62
Compressor discharge temperature (TD)
6
3
Compressor suction temperature (TS)
65
Heatsink temperature (THS)
6A
Operating current (x1/10)
6D
Outdoor heat exchange (coil)
temperature (TL)
F1
Compressor cumulative operating hours
(x100 h)
Procedure
1
Push the [
MENU] button to display
the menu screen.
2
Push and hold the [
MENU] button
and the [
] button at the same time
to display the “Field setting menu”.
→
Push and hold the buttons for more than 4
seconds.
3
Push the [
] / [
] button to
select “4. Monitor function” on the “Field
setting menu” screen, then push the “
S
et
Set” [
F2
F2] button.
→
Push the [
] / [
] button to
select the code to check data.
4
Push the [
CANCEL] button to return
to the “Field setting menu” screen.