Function CODE No. (DN Code) table (includes all functions needed to perform applied control on site)
DN
Item
Description
At shipment
0001
Filter display delay timer 0000: None
0002: 2500H
0004: 10000H
0001: 150H
000
3
: 5000H
0001: 150H
0002
Dirty state of filter
0000: Standard
0001: High degree of dirt (Half of standard time)
0000: Standard
001E
Temp difference of
[AUTO] mode selection
COOL
→
HEAT,
HEAT
→
COOL
0000: 0 deg
(For setup temperature, reversal of COOL / HEAT by } (Data value) / 2)
0010: 10 deg
to
000
3
:
3
deg
(Ts
±1.5)
0006
Heating temp shift
0000: 0 °C
0002: +2 °C
0001: +1 °C
0010: +10 °C
(Up to +6 recommended)
to
0000 : 0°C
002E
HA terminal (CN61)
select
0000: Usual
0002: Fire alarm input
0001: Leaving-ON prevention control 0000: Usual
(HA
terminal)
002A
Selection of option/Trouble
input (TCB-PCUC2E: CN
3
)
0000: Filter input
0002: None
0001: Alarm input (Air washer, etc.) 0002: None
002
8
Automatic restart of
power failure
0000: None
0001: Restart
0000: None
0014
Group address
0000: Individual
0002: Follower unit of group
0001: Header unit of group
00
99
: Unfixed
001
9
Louver type
(Air direction adjustment)
0000: No louver
0004: (4-way Air Discharge Cassette type)
0001: Swing only
0001: Swing only
0011
Indoor unit capacity
0000: Unfixed
0001 to 00
3
4
According to capacity
type
0012 Line address
0001: No.1 unit
00
3
0: No.
3
0 unit
to
00
99
: Unfixed
00
3
2 TA sensor selection
0000: Body TA sensor
0001: Remote controller sensor
0000: Body TA sensor
00
33
Temperature unit select 0000: °C
0001: °F
0000: °C
00
3
1 Ventilating fan control
0000: Unavailable
0001: Available
0000: Unavailable
00B
3
Soft cooling
0000: Unavailable
0001: Available
0001: Available
0077 Dual set point
0000: Unavailable
0002: Available
0000: Unavailable
001
3
Indoor unit address
0001: No.1 unit
0064: No.64 unit
to
00
99
: Unfixed
Type
0010
001
3
: (Floor Standing Type)
001
3
:
(Floor Standing Type)
000F
Cooling only
0000: Heat pump
0001: Cooling only (No display of [AUTO] [HEAT])
0000: Heat pump
000
3
Central control address 0001: No.1 unit
00
99
: Unfixed
0064: No.64 unit
to
00
99
: Unfixed
002B
Thermostat ON output
(TCB-PCUC2E)
0000: Indoor unit
thermostat
ON
0001: Output of compressor ON
signal
reception
to
0000: Indoor unit
thermostat
ON
0060
Timer setting
(wired remote controller)
0000: Available (can be performed) 0001: Unavailable
(cannot be performed)
0000: Available
00C2
Current demand X
%
to outdoor unit
0050 : 50
%
0100 : 100
%
to
0075 : 75
%
00D1
Existence of
8
˚C heating
operation function
0000 : Invalid (Impossible)
0001 : Valid (Possible)
0000 : Invalid
(Impossible)
00F6
Presence of Application
control kit
(TCB-PCUC2E)
0000: None
0001: Exist
0000: None
00D0
Whether the power
saving mode can be set
by the remote controller
0000: Invalid
0001: Valid
0001: Valid