– 72 –
CODE No. (DN)
0001
Item
Table 1.
S
ettin
g
data (CODE No. table (example))
S
ettin
g
data
Factory-
s
et value
Filter
s
ign lighting time
Depending on Type
0002
Filter poll
u
tion level
0000:
s
t
a
nd
a
rd
0003
Centr
a
l control
a
ddre
ss
0099: Not determined
0006
He
a
ting
su
ction temper
a
t
u
re
s
hift
Depending on Type
000F
Cooling only
0000: He
a
t p
u
mp
0010
Type
Depending on model type
0011
Indoor
u
nit c
a
p
a
city
Depending on c
a
p
a
city type
0012
S
y
s
tem
a
ddre
ss
0099: Not determined
0013
Indoor
u
nit
a
ddre
ss
0099: Not determined
0014
Gro
u
p
a
ddre
ss
0099: Not determined
0019
Lo
u
ver type (wind direction
a
dj
us
tment)
Depending on Type.
008B
Correction of high he
a
t feeling
0000: None
00D1
8 ˚C oper
a
tion 0000:
None
0028
Power f
a
il
u
re
au
tom
a
tic recovery
0000: None
005D
High ceiling
S
W
0000:
S
t
a
nd
a
rd
0077
D
ua
l
s
et point
0000: Un
a
v
a
il
ab
le
00B3
S
oft cooling
0001: Av
a
il
ab
le
0031
Ventil
a
tion f
a
n (
s
t
a
nd
a
lone)
0000: Not
a
v
a
il
ab
le
0032
S
en
s
or
S
W
0000: Body
s
en
s
or
0060
Timer
s
etting (wired remote controller)
0000: Av
a
il
ab
le
00D0
Remote controller oper
a
tion
sa
ve f
u
nction
0001: En
ab
le
00F6
Pre
s
ence of Applic
a
tion control kit
0000: None
002B
Thermo
s
t
a
t o
u
tp
u
t
S
W
0000: Thermo
s
t
a
t ON
002A
S
election of option / tro
ub
le inp
u
t
0002: H
u
midifier
002E
S
election of HA termin
a
l
0000: Norm
a
l (HA termin
a
l)
001E
Temper
a
t
u
re r
a
nge of cooling/he
a
ting
au
tom
a
tic
S
W control point
0003: 3 ˚C (T
s
±1.5)
00C2
Dem
a
nd
s
etting
(o
u
tdoor
u
nit c
u
rrent dem
a
nd)
0075: 75 %
Table 2. Type: CODE No. 10
Table 3.
Indoor unit capacity: CODE No. 11
S
ettin
g
data
0001
∗
1
0013
∗
2
Type
Type name abb.
S
ettin
g
data
Type
4-w
a
y C
ass
ette Type
Floor
S
t
a
nding Type
Di
sab
le
56
80
110
140
160
0000
∗
0009
0012
0015
0017
0018
RAV-GM
∗∗∗
UT
∗
RAV-RM
∗∗∗
FT
∗
∗
1 EEPROM initial value on the P.C. board for indoor unit
servicing.
∗
2
CAUTION
<Model name: RAV-RM
∗∗∗
FT
∗
>
For above models, set the CODE No. to “00CE” and the
setting data “0000” (initial) to “0001”.
∗
EEPROM initial value on the P.C. board
for indoor unit servicing.