– 68 –
[1] Setting data read out from EEPROM
(Stop the operation of the unit.)
1
Push the
[
MENU]
button to display the menu
screen.
2
Push and hold the
[
MENU]
button and the
[
]
button at the same time to display the
“
Field setting menu
”.
• Push and hold the buttons for more than 4 seconds.
3
Push the
[
] / [
]
button to select
“7. DN setting”
on the
“Field setting menu”
screen,
then push the
“
S
et
Set” [
F2
F2]
button.
• When the group control is used, all the indoor units
connected into the system are displayed on the screen.
4
Push the
“
Unit
Unit” [
F1
F1]
button to select
indoor unit in which you want to read out setting data in
the EEPROM.
• The selected unit changes as follows each time the button
is pushed:
Address is displayed here.
6. Setting timer operation mode
7. DN setting
8. Reset power consumption data
Field setting menu(2/2)
Return
Set
DN setting
Return
1-1
1-2
2-1
2-2
3-1
3-3
Set
Unit
DN setting
Code
(DN)
Data
1-1
Return
0001
0000
Fix
<
>
5
Push the
“
S
et
Set” [
F2
F2]
button.
• The setting display for the selected unit is displayed.
• The fan and louver of the indoor unit operate.
6
Push the
[
] / [
]
to set “
DN code
” to
[0001]
, then write down the setting data to be
displayed.
(Filter sign lighting time)
7
Repeat the operation of
1
to
6
, then write down the
setting data like
Table 1. Setting data
(CODE No. table
(example)).
∗
The Code No.(DN) are ranged in order of No., which may
be sometimes skipped.
8
After writing down all the setting data, push the
“
S
et
” [
F2
F2]
button.
• The setting display for the selected unit is displayed.
• When the group control is used, the fan and louver of the
selected indoor unit operate.
9
Push the
[
MENU]
button to set the other
“Code(DN)”
and
“Data”
. After
“Continue?”
is
displayed on the screen, push the
“
No
No”
[
F2
F2]
button to finish the setting operation. “
Setting” appears on the screen for a while, then the
screen returns to the “Field setting menu” screen.
1-1
1-2