6. External view of P.C. board assembly
7. Address setup
In addition to set up the central control address, it is necessary to change the indoor unit number.
(Line/Indoor/Group address). For details, refer to 1:1 model connection interface Installation Manual.
8-3. How to Set up Central Control Address Number
When connecting the indoor unit to the central control remote controller using 1:1 model connection interface,
it is necessary to set up the central control address number.
• The central control address number is displayed as the line No. of the central control remote controller.
How to set up from indoor unit side by remote controller
<Procedure>
Perform setup while the unit stops.
Termin
a
tor (
S
W01)
52
85
1
Push the [
MENU] button to display the menu screen.
2
Push and hold the [
MENU] button and the [
] button at the same time to display
the “Field setting menu”.
→
Push and hold the buttons for more than 4 seconds.
3
Push the [
] / [
] button to select “7. DN setting” on the “Field setting menu”
screen, then push the “
S
et
Set” [
F2
F2] button.
→
The fan and louver of the indoor unit operate.
When the group control is used, the fan and louver of the selected indoor unit operate.
→
Move the cursor to select “Code(DN)” with the “
<
<” [
F1
F1] button, then set “
0003
” with the
[
] / [
] button.
→
Move the cursor to select “Data” with the “
>
>” [
F2
F2] button, then set “Data” with the [
] / [
] button.
The setup data is shown in the table below (Table 1)
.
4
Push the [
MENU] button to set the other Code(DN) and Data. After “Continue?” is
displayed on the screen, push the “
No
No” [
F2
F2] button to finish the setting
operation.
“ Setting” appears on the screen for a while, then the screen returns to the “Field setting
menu” screen.