• Insert the soft socket of the supplied flexible hose into the connecting port of the drain pipe.
• Align the supplied hose band to the pipe connecting port end, and tighten.
• Connect the hard socket (Procured locally) to the hard socket side of the supplied flexible hose which has been installed.
• Connect the drain pipes (Procured locally) in turn to the connected hard sockets.
Connection of flexible hose
REQUIREMENT
• Fix the soft socket with the supplied hose band, tighten at the upper position of the unit.
• The supplied flexible hose can bend up to a maximum of 45°.
Connection of drain pipe
REQUIREMENT
• Using a adhesive agent for vinyl chloride, connect the hard vinyl chloride pipes so that water does not leak.
• Allow sufficient time for the adhesive to set and harden. (Refer to the instructions of the adhesive.)
NO GOOD
OK
max
45°
max
45°
Riser (Trap)
90° Bend
Socket for VP25 vinyl chloride pipe
(Local procure)
VP25 vinyl chloride
pipe (Local procure)
Flexible hose
(Accessory)
Align the attached hose band to the
end of hose, set the tightening position
upward, and then tighten it.
Drain pipe
connecting port
(Transparent)
Indoor unit body