– 59 –
32
22
Outdoor
temp.
(˚C)
Powerful Cool mode
Cool mode
20
Fan mode
Heat mode
(5) Louver control
The vertical air flow louvers are automatically set
to heating position or heat memory position.
When the compressor is turned off by high-temp.
release control, the vertical air flow louvers close
once and then return to the position of previous
time.
8-2-5. Auto Operation
(1) As shown in Fig. 8-2-10, the operation mode
(COOL, DRY, HEAT) is selected according to the
outside temperature when the operation has
started.
The operation in Fan mode continues until an
operation mode is selected.
If the room temperature is 20°C or higher when
“AUTO” operation started within 2 hours after
“HEAT” operation had stopped, select an opera-
tion mode after Fan operation of ultra low fan.
In AUTO operation, the set temperature of each
operation can be corrected by the remote
controller in the range of
△
Ts = ± 5°C.
Fig. 8-2-10
(2) After selecting the operation mode (COOL, DRY,
HEAT), select an operation mode again when a
status that the compressor was turned off by the
room temperature or outside air temperature
continues for 15 minutes.
(3) After selecting DRY operation, a status that the
room temperature is the set temp. –2°C contin-
ues for 15 minutes, select an operation mode
again.
(4) Powerful Cool mode control
When the outside temperature is above 32°C
and indoor temperature is above 28°C, select
Cool mode control. In Cool mode, the air flow
louver directs downward. When the room tem-
perature gains access to the set temperature, it
becomes cool memory position.
8-3. Temporary Operation
• Temporary Auto operation, existence of Auto
Restart, and Temporary Cooling operation can be
set by the TEMPORARY button of the indoor
controller.
TEMPORARY
TEMPORARY
button
8-3-1. Temporary Auto Operation
• When the TEMPORARY button is pushed, the
Auto operation with set temperature fixed at 24°C
starts. Controlling is same as that of Auto opera-
tion by the remote controller.
• When the TEMPORARY button is pushed again,
the operation stops.
• During Temporary Auto operation, operation by the
remote controller is accepted.
• Using the Auto Restart function, the Temporary
Auto operation starts when power failure is reset.
8-3-2. Temporary Cooling Operation
• When the TEMPORARY operation button keeps
pushed for 10 seconds, Cooling operation of which
compressor motor speed and the indoor fan speed
are fixed starts.
Compressor motor speed : 24.5 rps
Indoor fan speed : Low
• When the TEMPORARY operation button is
pushed again, the operation stops.
• Auto Restart function is unavailable.
Fig. 8-3-2
TEMPORARY button
Control
OFF
→
ON
Temporary Auto operation start
After pushing button
Auto Restart control select
for 3 seconds
After pushing button
Temporary Cooling
for 10 seconds
operation start