– 89 –
10-5-2. Wiring Failure (Interconnecting and Serial Signal Wire)
(1) Outdoor unit does not operate
1) Is the voltage between
and
of the indoor terminal board varied?
Confirm that transmission from indoor to outdoor is correctly performed based upon the following dia-
gram.
NOTE:
• Measurement should be performed 2 minutes and 30 seconds after starting of the operation.
• Be sure to prepare a diode for judgment.
(3) The outdoor unit stops 10 minutes to 1 hour after operation started, and an alarm is displayed.
(Discharge temp. error check code 03, 1E)
Gas leak
P.M.V. is defective.
Miswiring of connecting wires of indoor/outdoor units
Clogging of pipe and coming-off of TG, TC sensors
To item of Compressor does not operate.
(2) If the unit stops once, it does not operate until the power will be turned on again.
Gas circulation amount is down.
Measure gas pressure.
Gas shortage
Gas leak
Pipe clogging
Thermo. operation of compressor
Fig. 10-5-1
Normal time
: Voltage swings between DC15 and 60V.
Abnormal time
: Voltage does not vary.
(2) Outdoor unit stops in a little while after operation started
<Check procedure> Select phenomena described below.
(1) The outdoor unit stops 10 to 20 minutes after operation started, and 10 minutes or more are required to
restart the unit.
Red
White
Terminal board
S5277G
Tester
3
2
1
Terminal board at indoor side
S5277G or equivalent (G or J type)
(Diode with rated voltage of 400V
or more is acceptable.)